ComfortPoint
TM
Open System
9
EN1B-0498GE51 R0512
Terminals
ANALOG
INPUTS
ANALOG
OUTPUTS
GND
BINARY
INPUTS
1
B1
2
B2
3
B3
4
B4
5
B5
6
B6
7
B7
8
9 10 11 12
B8 B9
B10 B11 B12
13 14
14 15 16
AI1
AI2
AI2 AI3 AI4
17 18 19 20
AI5 AI6 AI7 AI8
25 26 27
21 22 23 24
28
AO5 AO6 AO7
AO1 AO2 AO3 AO4
AO8
41
G1
42
G2
74
73
72
71
24
V
~
24
V
~
0
COM
B
COM
A
78
77
76
75
24
V
~
24
V
~
0
COM
B
COM
A
J1
J2
J3
J4
J5
CO1
NO1
35
29
CO2
NO2
36
30
CO3
NO3
37
31
24 V RELAYS
CO4
NO4
38
32
CO5
NO5
39
33
CO6
NO6
40
34
R1
R2
R3
R4
R5
R6
EXTERNAL
24VAC FOR RELAY
COMMON
JUMPERS
JUMPERS
Fig. 9. Terminal assignment and internal connections of CPO-IO830A terminals
Table 9. Description of CPO-IO830A terminals
Terminal
Signal
LED
Comment
71, 75
COM a
Status
2-wire Panel Bus communication bus
72, 76
COM b
Status
2-wire Panel Bus communication bus
73, 77
24 V~
Power
Power supply
74, 78
24 V~0
Power
Power supply
1…7
BI1…7
1…7
Binary inputs 1…7
8…12
BI8…12
24…28
Binary inputs 8…12
13…20
AI1…8
--
Analog inputs 1…8
41, 42
GND
--
Ground. Both grounds are internally connected to each other and to 24 VAC0.
21…28
AO1…AO8
--
Analog outputs 1…8
29…34
NO1…6
29…34
Relays 1…6, normally-open contacts
35…39
IN1…5
--
Common contacts of relays 1…5. May be set to common supply voltage via
terminal 40 by inserting jumpers J1…J5 into their
lower
positions. When, in
contrast, a jumper is in the
upper
position (the so-called “parking position” = default
setting), the corresponding relay receives no supply voltage from terminal 40.
40
IN6
--
Common contact of relay 6, internally connected to the middle contact of jumpers
J1…J5. May be used to connect common supply voltage.