CM907-

TRV

 CHRONOTHERM

 

 

 

  

EN0H 8555 UK07 R0 09/06 

4

Special Features

 

Description

 

What to do if we wish this 
feature

 

Optimisation (Variable 
Start Time) 

Adaptive Intelligence 
recovery TM

 

The thermostat will adjust the start time in the 
morning/afternoon so the desired temperature is 
reached by the start of the program period e.g. Time 
7:00, Temp 21 

o

C. The thermostat will monitor the 

accuracy of the start up and use this information to 
modify the calculation for the following day by changing 
the ramp rate (initial 3 K/hr) .The system will restrict the 
start time to a max of 2 hours.  

Note:

 Optimisation will not work in cooling mode. 

Set parameter n.8, category 1 in the 
installer set-up mode to 1. 

AM-PM/ 24hr Display 

Change display format (default 24hr). 

Set parameter n.1, category 1 in the 
installer set -up mode to 12. 

Pump exercise 

When enabled the Pump Exercise will switch the relay 
on for 1 minute at 12:00 if the relay has not been 
switched on since 12:00 the previous day. 
While in Holiday mode the Pump Exercise feature, if 
enabled, will operate. 

Set parameter n.5, category 2 in the 
installer set -up mode to 1. 

Upper Temperature Limit 

The normal upper temperature limit of 35

 o

C can be 

reduced down to 21

 o

C to save the homeowner energy. 

Useful if the homeowner rents to tenants. 

Set parameter n.6, category 1 in the 
installer set -up mode to the desired 
limit. 

Lower Temperature Limit   The normal lower temperature limit of 5

 o

C can be 

increased up to 21

 o

C to protect the inhabitants from 

cold. Useful if the inhabitants include the elderly, 
children or disabled. 

Set parameter n.7, category 1 in the 
installer set -up mode to the desired 
limit. 

Temperature Offset 

If the thermostat is located in a hot/cold location and 
cannot be moved because of wiring then the measured/ 
displayed temperature can be adjusted by +/- 3

 o

C. 

Useful if the homeowner wants the reading to match 
another appliance temperature display. 

Set parameter n.12, category 1 in the 
installer set -up mode to the desired 
offset value. 

Proportional Band Width 

Can be adjusted up to 3

 o

C (default is 1.5 

o

C) to provide 

better temperature control (less overshoot).  
Useful for: 
a.  Well insulated homes with over-sized heating 

systems. 

b.  Air systems with fast response. 

Set parameter n.13, category 1 in the 
installer set -up mode to the desired 
value. 

 
 

Optional 
Accessories

 

Description

 

What to do if we wish this 
feature

 

Outside Temperature 
Sensor 

(F42010971 001)

 

An Outside Temperature Sensor can be fitted, allowing 
the homeowner to display the outside temperate on the 
thermostat display by pressing the INFO 

i

 button. 

The 

thermostat will read the outside temperature every 10 
minutes. Outside temperature display range is from -30

 

o

C to +45

 o

C. The sensor can be connected up to 50 

meters from the unit. 

1.  Fit the sensor (instructions 

included in the sensor package). 

2.  Set parameter n. 10, category 1 in 

the installer set-up mode to 1. 

Remote Temperature 
Sensor 

(F42010972 001)

 

A Remote Temperature Sensor can be fitted, allowing 
the thermostat to control the temperature from another 
room or space, where it is inconvenient to locate the 
thermostat. It will read the remote sensor every 1 
minute. The sensor can be connected up to 50 meters 
from the unit. Useful for commercial premises where the 
public may tamper with the product. 

1.   Fit the sensor (instructions 

  included in the sensor package). 

2.   Set parameter n. 10, category 1 in 

the installer set-up mode to 2. 

 

Summary of Contents for CM901

Page 1: ... temperature in the house The TRV mode can either be pre programmed or switched manually TRV button allows activation or cancellation of the TRV mode manually whenever this type of control is required Party feature that temporarily maintains a selectable constant temperature for 1 23 hours then returns to normal operation Holiday button that provides energy savings by reducing to a constant temper...

Page 2: ...our Room Temperature display range From 0 o C to 50 o C Control form P I Proportional Integral Minimum ON time 10 of cycle time min one minute adjustable to 2 to 5 min see installer set up Cycle rate Selectable by application see installer set up Wiring Terminal block capable of accepting wires up to 2 5 mm 2 Wire access Mains wiring rear right Low voltage wiring rear right Dimensions 133 x 89 x 2...

Page 3: ...or 5 seconds Modify the cooling program as required Heat Pump Air conditioner 3 4 1 Set Minimum ON Time to 4 minutes 2 Set Cycle Hour to 3 2 Fan coil 6 1 No action required In Installer set up we can Set up specific applications Enable special features Establish support for optional accessories To enter the installer set up mode a Move the slider switch to the OFF position b Press and hold the INF...

Page 4: ...installer set up mode to the desired limit Temperature Offset If the thermostat is located in a hot cold location and cannot be moved because of wiring then the measured displayed temperature can be adjusted by 3 o C Useful if the homeowner wants the reading to match another appliance temperature display Set parameter n 12 category 1 in the installer set up mode to the desired offset value Proport...

Page 5: ...r Temp Limit 6 to 21 6 C to 21 C adjustment in 1 C steps 1 Optimisation 8 0P 0 Optimisation disabled 1 Optimisation enabled 1 Remote Control Setpoint e g via telephone module 9 tS 0 Disabled 1 Enabled 1 Second Temperature Sensor 10 SS 0 No sensor fitted 1 2 1 Outside Temperature Sensor fitted 2 Remote Temp Sensor fitted 1 Temperature Offset 12 tO 0 No offset 3 to 3 3 C to 3 C adjustment in 0 1 C s...

Page 6: ...r lights near doors or windows or in direct sunlight MOUNTING The CM907 TRV thermostat can be mounted directly on the wall surface or on an electrical wallbox WIRING The CM907 TRV thermostat is designed for fixed wiring only and must be installed in accordance with the latest l E E regulations Ensure the wiring connection to the supply is via a fuse rated at no more than 8 amps and a Class A switc...

Page 7: ...om EN0H 8555 UK07 R0 09 06 WIRING Description Model Logo Literature Availability Spec Sheet 7 day programmable thermostat Remote Temperature Sensor Outdoor Temperature Sensor CMT907A1082 F42010972 001 F42010971 001 Honeywell Honeywell French Dutch Multi lingual Multi lingual Aug 06 Sep 06 Sep 06 ENOH8555 ENOH8554 ENOH8553 ORDERING SPECIFICATION ...

Reviews: