CIPer
TM
MODEL 50 CONTROLLER
–
INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
78
NTC 10 k
Ω
(Type II) Temperature
NTC 10 k
Ω
(Type II) Temperature
Temp.
[°F]
Temp.
[°C]
Resistance
Terminal
voltage [V]
Temp.
[°F]
Temp.
[°C]
Resistance
Terminal
voltage [V]
50
10
19.898
4.209
165.2
74
1.531
0.575
51.8
11
18.968
4.103
167
75
1.481
0.557
53.6
12
18.087
3.998
168.8
76
1.433
0.541
55.4
13
17.252
3.894
170.6
77
1.387
0.524
57.2
14
16.46
3.792
172.4
78
1.342
0.508
59
15
15.708
3.69
174.2
79
1.299
0.493
60.8
16
14.995
3.591
176
80
1.258
0.478
62.6
17
14.319
3.492
177.8
81
1.218
0.464
64.4
18
13.678
3.396
179.6
82
1.179
0.45
66.2
19
13.068
3.3
181.4
83
1.142
0.436
68
20
12.49
3.207
183.2
84
1.107
0.423
69.8
21
11.94
3.115
185
85
1.072
0.411
71.6
22
11.418
3.025
186.8
86
1.039
0.399
73.4
23
10.921
2.937
188.6
87
1.007
0.387
75.2
24
10.449
2.85
190.4
88
0.976
0.375
77
25
10
2.767
192.2
89
0.947
0.365
78.8
26
9.572
2.684
194
90
0.918
0.354
80.6
27
9.165
2.603
195.8
91
0.89
0.344
82.4
28
8.777
2.524
197.6
92
0.863
0.334
84.2
29
8.408
2.447
199.4
93
0.838
0.324
86
30
8.057
2.372
201.2
94
0.813
0.315
87.8
31
7.722
2.299
203
95
0.789
0.306
89.6
32
7.402
2.228
204.8
96
0.765
0.297
91.4
33
7.098
2.159
206.6
97
0.743
0.289
208.4
98
0.721
0.28
210.2
99
0.7
0.276
212
100
0.68
0.265