CIPer
TM
MODEL 50 CONTROLLER
–
INSTALLATION AND COMMISSIONING INSTRUCTIONS
31-00233-02
32
15
BO7
Binary output 7. N.O. relay contact switching input power
connected to terminal 16
X
16
IN7
Relay contact for BO7
X
17
IN8
Relay contact for BO8
X
18
BO8
Binary output 8. N.O. relay contact switching input power
connected to terminal 17
X
19
GND
Ground terminal (see NOTE below)
X
20
AO1
Analog output 1
X
21
AO2
Analog output 2
X
22
AO3
Analog output 3
X
23
AO4
Analog output 4
X
24
GND-1
ref. GND of RS485-1 (isolated)
X
25
485-1+
"+" signal for RS485-1 (isolated)
X
26
485-1-
"-" signal for RS485-1 (isolated)
X
27,28
not used
-
29
485-2+
"+" signal for RS485-2 (non-isolated)
X
30
485-2-
"-" signal for RS485-2 (non-isolated)
X
31
GND-2
ref. GND of RS485-2, int. conn. with 24V-0 (term. 1) and system
GND (term. 19+37)
X
32
-
not used
-
33
BI1
Binary input 1 (static dry contact) / pulse counter (fast totalizer)
X
34
BI2
Binary input 2 (static dry contact) / pulse counter (fast totalizer)
X
35
BI3
Binary input 3 (static dry contact) / pulse counter (fast totalizer)
X
36
BI4
Binary input 4 (static dry contact) / pulse counter (fast totalizer)
X
37
GND
Ground terminal (see NOTE below)
X
38
UI9
Universal input 9 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
39
UI10
Universal input 10 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
40
UI1
Universal input 1 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
41
UI2
Universal input 2 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
42
UI3
Universal input 3 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
43
UI4
Universal input 4 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
44
UI5
Universal input 5 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
45
UI6
Universal input 6 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
46
UI7
Universal input 7 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
47
UI8
Universal input 8 (for NTC10k
Ω
/ NTC20k
Ω
/ 0...10 V / slow BI)
X
NOTE
All AOs, UIs, and BIs share the same ground potential. It is thus possible to connect just one combined
GND signal for all AOs, UIs, and BIs. Auxiliary terminals may be used if needed.