background image

T8624D CHRONOTHERM

®

 IV DELUXE PROGRAMMABLE MULTISTAGE THERMOSTATS

69-1412—1

4

Fig. 6. T8624D key locations and descriptions.

Using Thermostat Keys

The thermostat keys are used to:
• set current day and time,
• program times and setpoints for heating and cooling,
• temporarily override program temperatures, 
• display present setting, 
• configure Installer Setup, 
• check System Test,
• display outdoor temperature (select models),
• set the system operation, 
• set the fan operation. 

See Fig. 6 for the location of the keys.

SETTINGS

System and Fan Settings 

The system default setting is Heat and the fan default 
setting is Auto. Use the System and Fan keys to change 
the settings. See Fig. 7. The fan settings can be set for 
each program period individually. The system selection is 
for all the program periods.

System settings control the thermostat operation as 
follows:

Heat: The thermostat controls the heating.
Off: Both the heating and cooling are off.
Cool: The thermostat controls the cooling.
Auto: The thermostat automatically changes between 

heating and cooling operation, depending on the 
indoor temperature.

Fan settings control the system fan as follows:

On: Fan operates continuously.
Auto: Fan operates with equipment.

Fig. 7. T8624D System and Fan key locations.

NOTE: Always press the keys with your fingertip or  

similar blunt tool. Sharp instruments like a pen 
or pencil point can damage the keyboard.

Temperature Settings

Refer to Table 2 for the default program. If the daytime 
energy savings period is not used, press the period key 
(Leave or Return) until the time is blank. The fan setting 
feature is available on select thermostat models. See 
Owners Guide, form number 69-0940, for complete 
instructions on changing the program.

Table 2. Default Program Settings.

M14624

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Copy

INCREASE TEMPERATURE 
SETTING OR SCROLL 
FORWARD THROUGH 
INSTALLER SETUP OPTIONS

DECREASE TEMPERATURE 
SETTING OR SCROLL 
BACKWARD THROUGH 
INSTALLER SETUP OPTIONS

DISPLAY INFORMATION
SUCH AS PRESENT 
SETTINGS AND OUTDOOR 
TEMPERATURE

RETURN TO 
NORMAL
OPERATIONS

ENTER 
INDEFINITE 
OR TIMED 
HOLD MODE

SET CURRENT 
DAY AND TIME

SET CURRENT OR
PROGRAM DAY

CHANGE BETWEEN 
DAYLIGHT SAVINGS 
AND STANDARD TIME

INCREASE TIME SETTING
OR SCROLL FORWARD 
THROUGH INSTALLER SETUP 
AND SYSTEM TEST

DECREASE TIME SETTING OR 
SCROLL BACKWARD THROUGH 
INSTALLER SETUP AND SYSTEM TEST

COPY ONE PROGRAMMED 
DAY TO ANOTHER DAY

SET WAKE TIMES 
AND SETPOINTS

CHANGE BETWEEN 
HEATING AND COOLING 
SETPOINTS 

SET LEAVE TIMES 
AND SETPOINTS

SET RETURN TIMES 
AND SETPOINTS

SET SLEEP TIMES 
AND SETPOINTS

SELECT SYSTEM 
OPERATION 

SELECT FAN 
OPERATION 

Period

Time

Heat 

Setpoint

Cool 

Setpoint

Fan 

Setting

Wake

6:00 AM 70°F

(21°C)

78°F 
(25.5°C)

Auto

Leave

8:00 AM 62°F

(16.5°C)

85°F 
(29.5°C)

Auto

Return 6:00 PM 70°F

(21°C)

78°F 
(25.5°C)

Auto

Sleep

10:00 PM 62°F

(16.5°C)

82°F 
(28°C)

Auto

M14625

Hold Temp

Run

Program

Copy

Daylight

Time

Set Current

Day/Time

System

Fan

Time

Set Program

Day

System

Fan

Wake

Leave

Return

Sleep

Heat/Cool

Settings

Summary of Contents for CHRONOTHERM IV T8624D

Page 1: ...ION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to ...

Page 2: ...lush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening 5 Loosely insert the mounting screws into the holes 6 Tighten mounting screws Fig 2 Mounting the wallplate WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 for typical hookup A letter code is located near each terminal for identification CAUTION Electrical Shoc...

Page 3: ...ate W2 L1 HOT L2 M11309 FAN RELAY Y1 G C THERMOSTAT RC HEAT RELAY 1 R W1 L1 HOT L2 COMPRESSOR CONTACTOR 1 Y2 COMPRESSOR CONTACTOR 2 HEATING TRANSFORMER COOLING TRANSFORMER HEAT RELAY 2 OT OT B HEAT DAMPER OUTDOOR SENSOR COOL DAMPER O 2 2 3 3 3 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM CAN ...

Page 4: ...ram If the daytime energy savings period is not used press the period key Leave or Return until the time is blank The fan setting feature is available on select thermostat models See Owners Guide form number 69 0940 for complete instructions on changing the program Table 2 Default Program Settings M14624 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep...

Page 5: ...mbers are shown on the device Example If thermostat does not have a System key Installer Setup Number 12 will not be displayed Review Table 3 factory settings and mark any desired changes in the Actual Setting column When Installer Setup is complete review the settings to confirm that they match the system M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait ...

Page 6: ...mperature is displayed 1 Outdoor temperature is displayed Needs a C7089B1000 Outdoor Temperature Sensor to operate Not Used 25 thru 29 Deadband 30 3 Heating and cooling setpoints can be set no closer than 3 F 1 5 C 4 thru 10 Heating and cooling setpoints can be set no closer than the chosen value 4 4 F 2 C 5 5 F 2 5 C 6 6 F 3 C 7 7 F 3 5 C 8 8 F 4 C 9 9 F 4 5 C 10 10 F 5 C Not Used 31 and 32 Minim...

Page 7: ...ture 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Display adjusts to 3 F lower than actual room temperature Furnace Air Filter Timer 43 2 30 days System run time 0 1 3 4 0 Off 1 10 days 3 60 days 4 120 days Time counted when heat cool or fan is running Humidifier Pad Monitor 44 0 Off 1 2 3 1 90 days 2 180 days 3 365 days ...

Page 8: ...isplayed before the 10 appears See Fig 10 and 11 Table 4 Tests Available In Installer System Test Fig 10 Display of all the segments of the LCD Fig 11 Display of test number Refer to Table 5 for the directions and results of the specific tests Press Time to advance to the next test and Time to go back to the previous test Press Run Program to exit the system test M14622 Time Set Program System Fan...

Page 9: ... Stage one heat comes on The system fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 11 Stage two heat turns off 10 Stage one heat and system fan turn off Cooling Equipment System Test Time 30 Change from heating to cooling equipment System Test 31 Stage one cool and system fan come on 32 Stage two cool comes on Stage one cool and system fan remain on 31 Sta...

Page 10: ... soft ware identification code Example 02 software ID code 2 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes with out any key presses CHECKOUT Outdoor...

Page 11: ...t come on No power to the thermostat Check for 24 Vac between R and W terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any...

Page 12: ...gisters Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperature display is incorrecta Outdoor sensor is connected incorrectly Refer to C7089B1000 Installation Instru...

Reviews: