Honeywell
CD3000M-3PH up to 90A
User’s Manual
www.honeywell.com/imc 6
2. Technical specifications
2.1 General Features:
Operating temperature
0÷40°C for higher temperature see derating curve
Voltage power supply
24V minimum, 480V max and 600V on request
Input signal
SSR
4÷20 mA
0÷10V
potentiometer (10k ohm)
customer configurable with automatic zero/span calibration
Firing mode
One of these firing modes can be configured on line via serial port
Zero Crossing (ZC)
Burst Firing (BF)
Auxiliary voltage supply
230V range (230 ±15%) 10VA
460V range (380 –15%) ÷ (460 +15%); 10VA
(sincronized with supply Voltage)
Fan voltage supply
230V range (230 ±15%) 10VA
460V range (380 –15%) ÷ (460 +15%); 10VA
(sincronized with supply Voltage)
Heather break alarm
Discrimination better than 20%. Circuit microprocessor based to
diagnose partial or total load failure and short circuit on Thyristors.
Latching alarm plus reset. Relay output 0,5A at 125V
Line Drop Voltage
Automatic compensation ±15% of supply voltage with analog input
Mounting
Bulk head mounting
Protection IP20
2.2 Input features
Input signal
Maximum
current drain
Input
Impedance
ON condition
OFF condition
SSR
5mA constant current
≥
4V - max 30V
≤
1V
Analog 0÷10V
-
8200 ohm
Analog 4÷20mA
-
100 ohm
Potentiometer
10K ohm
8200
ohm