
Honeywell
CD3000M-3PH up to 90A
User’s Manual
www.honeywell.com/imc 48
10.4.4 Firing type
Parameter 125L
Operations:
Read/Write
Meaning:
Selection table of firing modes.
Value Type
Option
H L
0 1 Zero
Crossing
-
0 2 Single
Cycle
-
0 3 Burst
-
1
1
Zero Crossing
Soft Start
1 2 Single
Cycle
-
1
3 Burst
Soft Start
2
1 Zero Crossino
Delay trigger
2 2 Single
Cycle
2
3 Burst
Delay triggering
2
4 Phase angle
Soft start
10.4.5 Soft start time
Parameter 125H
Operations:
Read/Write
Meaning :
Time
Soft Start Time
Par 125H x 5msec
OUT
It’s correspond to a value in points (0 – 255, 0 – FF Hex).
Each step is 5msec .
The unit start in phase angle mode with a ramp starting from
zero up to full voltage in a presetted and Adjustable time.
The time is setted by this parameter.
Value of this parameter must be less than cycle time.
For burst firing:
Value of this parameter must be less than:
50Hz -> 20msec
x Number of cycles (Parameter 126L).
60Hz -> 16,6msec x Number of cycles (Parameter 126L).