10.4.9 Cycle time
Parameter 127H
Operations:
Read/Write
Meaning:
It’s a value in points (0 – 255, 0 – FF Hex).
Each step is 50msec .
Cycle Time
Time
20%
ON
OFF
50%
70%
100%
When single cycle (SC) and burst firing (BF) is used must be setted at 240 (FO Hex)
When SSR input is used set at 240 (FO Hex)
When is used zero crossing (ZC) represents the cycle time
(ON time + OFF time, default 60(3C Hex) )
10.4.10 Number of half periods for DT firing
Parameter 128L
Operations:
Read/Write
Meaning:
Must be setted at 1.