9.3.5 Output Power
Parameter 5
Command from controller
Operations:
Read
Meaning:
It rapresent a value in points (0-255, 0-FF Hex) and it’s the power demand in % of controller.
Example:
0%
= 0
0 (Hex)
50%
= 128
80 (Hex)
100%
= 255
FF (Hex)
Command via RS485
Operations :
Read/Write
Meaning:
It’s a value in points (0-255, 0-FF Hex)
It’s power set point setted in thirst buffer
Example:
0%
= 0
0 (Hex)
50%
= 128
80 (Hex)
100%
= 255
FF (Hex)
9.3.6 Power adjust
Parameter 6
Operations:
Read/Write
Meaning:
Its’ a value in points (0-255, 0-FF Hex)
Its’ a scaling factor of power demand
Example 1:
0%
= 0
50% = 128
100% = 255
Example 2:
•
Output Power :100
Power Limit :100
-> Power real : 100
•
Output Power :100
Power Limit :50
-> Power real : 50
•
Output Power :80
Power Limit :50
-> Power real : 40
100
Power Adjust = 100%
Power Adjust = 80%
Power Adjust = 40%
80
60
40
20
0
40
20
60
100
80
Input %
OUT %