7.5 Delay TriBurst
Firing (DT + BF)
It's used to switch ON-OFF primary of
transformer coupled with resistive load on
secondary. It's used to prevent inrush surge
current when zero voltage switching is used
and to avoid fuse blowing. Every time that
auxiliary voltage supply of PCB board is
switched ON, the unit starts in phase angle
for 1 sec., after witch it switches OFF when
the supply waveform is negative and starts
again when is positive, giving a delay on
triggering signal on first halt positive cycle. If
circuit board is maintained under voltage
phase angle start is not used.
LINE VOLTAGE
T
V
LOAD SUPPLY
T
7.6 Phase Angle ( PA)
With Phase Angle is possible to control the
power to the load allowing to Thyristor to be
in conduction for a variable part of the
voltage supply halt cycle. The load power
can be adjusted from 0 to 100% as a
function of analog input signal, normally
delivered by temperature controller or by
potentiometer. Normal it's used with inductive
loads. The only disadvantage with phase
angle is the generation of interferences that
can be reduced with filters.