Honeywell
CD3000M-1PH from 125A to 700A
User’s Manual
www.honeywell.com/imc
40
9.3 Word parameters
Parameter
N.
Notes
Heater nominal current
1
Read only
Set-point HB
2
Read /write
Status Table (shown in Tab 2.1.2)
3
Read only
Comand Table (shown in Tab 2.1.3)
4
Read /write
Output Power (0 – FFH)
5
Read - (Write if BIT1in Command table i = 1)
(0->0% - FF->100%)
Power Adjust (0 – FFH)
6
Read -- (Write if BIT1in Command table i = 1)
(0->0% - FF->100%)*
9.3.1 Heater nominal current
Parameter 1
Operation:
Read
Meaning:
It correspond at one value in points (0-255,0-FF Hex).
It represents average current value flowing into thyristors.
Value depends on current transformer ratio that is different from one size to the other one (see
below table)
Nominal current
(A)
Zero (0 , 0 Hex)
(A)
Max ( 255 , ff Hex)
(A)
3,5
0
3,5
15
0
25
25
0
25
35
0
50
45
0
50
60
0
100
90
0
100
110
0
100