C7961E,F DYNAMIC SELF-CHECK ULTRAVIOLET FLAME DETECTOR

65-0267-09

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, 

or would like to comment on our products or services, please write or phone:

1.

Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

3.

http://customer.honeywell.com or http://customer.honeywell.ca

International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech 

Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.

SPECIFICATIONS

IMPORTANT

The specifications in this publication do not include 

normal manufacturing tolerances. Therefore, this unit 

may not exactly match the specifications listed. This 

product is tested and calibrated under closely con-

trolled conditions, and minor differences in perfor-

mance can be expected if those conditions are 

changed.

Models:

C7961E Dynamic Self-Check Ultraviolet Flame Detector.

C7961F Dynamic Self-Check Ultraviolet Flame Detector. 

(Same as C7961E except with explosion-proof housing for 

use in hazardous locations).

Electrical Ratings:

Voltage and Frequency: 120 Vac (-15%, +10%), 50/60 Hz.

Ambient Operating Temperature Ratings 

(Outside the Case): 

-40°F to 175°F (-40°C to 80°C).

Storage Temperature Ratings: 

-60°F to 175°F 

(-50°C to 80°C).

Housing:

C7961E: Violet, cast-aluminum cover. Separate mounting 

flange (with heat block) and faceplate provide heat insula-

tion and sealoff. 

Meets NEMA 4 enclosure requirements (indoor, outdoor pro-

tection; rain-tight, dust-tight, hose-directed water protec-

tion). 

C7961F: Explosion-proof, two-piece, violet, cast aluminum. 

Pressure Rating of Quartz Viewing Window:

C7961E: 20 psi (138 kPa), see Replacement Parts.

C7961F: 100 psi (690 kPa). 

Pressure Rating of Quartz Focusing Lens: 

20 psi 

(138 kPa), see Accessories.

Mounting: 

C7961E: Mounting flange with 3/4 in. NPT or 1 in. 

NPT internal threads for attaching to sight pipe.

C7961E1014, C7961E1022: Mounting flange with 1 inch NPT 

internal threads for attaching to sight pipe.

C7961F: Pipe union with 1 inch NPT internal threads for 

attaching to sight pipe.

Wiring Connections:

Leadwire: Models with NEC Class 1 color coded 

(C7961E1006, C7961E1014). 

Length: 8 ft (2.4m).

Threaded Leadwire Faceplate Opening:  

1/2-14 NPSM 

internal threads for attaching conduit.

Connector: 

 Models with Molex Woodhead 1R5006A20A120 

(formerly Brad Harrison® 41310 Connector) (C7961E1022, 

C7961E1030).

Dimensions:  

See Fig. 1.

Weight:

C7961E: 2.6 lbs (1.2 kg).

C7961F: 14.5 lbs (6.6 kg).

SIL 3 Capable:

The C7961 when used with a R7851C self-check amplifier in 

Relay Module EC7810A, 20A, 30A, 40L, 50A; 

RM7800[E,G,L,M], 30A, 38[A,B,C], 40[E,G,L,M] 50A, 

90[A,B,C,D], 97[A,C], 98A is SIL 3 Capable in a properly 

designed Safety Instrumented System. See form number 

65-0312 for Certificate Agreement.

Approvals:

Underwriters Laboratories Inc. Listed: File Number MP268, 

Guide Number MCCZZ.

Canadian Standards Association Certified: Pending.

Factory Mutual Approved: 14740.01.

SwissRe (formerly Industrial Risk Insurers) Acceptable.

C7961F: For use in hazardous locations; Class I, Groups C 

and D; Class II, Groups E, F, and G; File no. E34649.

Replacement Parts:

190971G Shutter Assembly.

C7961E:

114372 Quartz Viewing Window; rated for 20 psi (138 

kPa).

114465 Gasket, silicone rubber; for installing viewing win-

dow (three required).

120739 Gasket, fiber-neoprene; heat insulation and 

seal-off for mounting flange.

C7961F:

122037 Quartz Viewing Window; rated for 100 psi 

(690 kPa).

Summary of Contents for C7961E

Page 1: ...Models available with Molex Woodhead 1R5006A20A120 Formerly Brad Harrison 41310 connector A swivel mount is available to facilitate flame sighting 40 F 40 C rated ultraviolet sensing tube Incorporates UV sensor tube checking feature used with R7851C Dynamic Self check Amplifiers High pressure 50 psi 345 kPa quartz viewing window magnifying lens and antivibration mount are available as accessories ...

Page 2: ...ets NEMA 4 enclosure requirements indoor outdoor pro tection rain tight dust tight hose directed water protec tion C7961F Explosion proof two piece violet cast aluminum Pressure Rating of Quartz Viewing Window C7961E 20 psi 138 kPa see Replacement Parts C7961F 100 psi 690 kPa Pressure Rating of Quartz Focusing Lens 20 psi 138 kPa see Accessories Mounting C7961E Mounting flange with 3 4 in NPT or 1...

Page 3: ...lues marked on the detector 4 Sight the detector so it does not respond to ignition spark 5 On multiburner installations each detector must respond only to the flame of the burner it is supervis ing Proper flame detector installation is the basis of a safe and reliable flame safeguard installation Refer also to the burner manufacturer instructions Carefully follow all instructions for the best pos...

Page 4: ...ge of the detector field of view If the temperature of the hot refractory causes the flame relay in the flame safeguard control to pull in re aim the sight pipe so the detector views a cooler area of the refractory Ignition spark is an intense source of ultraviolet radiation When installing the detector make sure it does not respond to ignition spark Single Burner Requirements The detector must ha...

Page 5: ...an installation locate each flame detector so that it has the best possible view of the first 30 percent closest to the burner nozzle the flame root it is supervising and the worst possible view of all other flames Fig 4 illustrates a critical detector application problem that requires flame discrimination Flame discrimination is accomplished for Detector A by repositioning it until the flame rela...

Page 6: ...the sight pipe and into the chamber The air pressure must be greater than the chamber pressure Swivel Mount To facilitate proper flame sighting use 118367A Swivel Mount ordered separately The swivel mount requires a reducer of the proper size to mount it onto the sight pipe It also requires a one inch close nipple for mounting to a C7961 with a one inch connector For 118367A Swivel Mount mounting ...

Page 7: ...ectrical ignition source in the event of a seal leakage 1 All wiring must comply with applicable local electrical codes ordinances and regulations Use NEC Class 1 wiring 2 Keep the flame signal leadwires as short as possible from the flame detector to the terminal strip or wiring subbase Capacitance increases with leadwire length reducing the signal strength The maximum permissible leadwire length...

Page 8: ...e when using direct spark ignition Also measure the flame signal at low and high firing rates and while modulating in between as applicable With the detector in its final position all required flame signals must be steady or stable and as specified in Table 1 If you cannot obtain the proper signal refer to the Troubleshooting section Pilot Turndown Test When the detector is used to prove a pilot f...

Page 9: ...satisfactorily completed TROUBLESHOOTING WARNING Electrical shock hazard Can cause serious injury or death Open the master switch to disconnect power before removing or installing the detector or its cover More than one disconnect may be involved Equipment Required A volt ohm meter with a minimum sensitivity of one megohm volt and a zero to five or ten Vdc scale is suggested When the Keyboard Disp...

Page 10: ... place to avoid losing them Fig 12 Replacing quartz viewing window or focusing lens Replacing Quartz Viewing Window or Focusing Lens C7961E Fig 12 IMPORTANT Use quartz window or lens Ordinary glass absorbs or filters out ultraviolet radiation 1 Open the master switch remove the detector from the sight pipe and remove the detector cover See appropri ate sections 2 Loosen the three screws holding th...

Page 11: ... to the faceplate and remove the flange Put the bolts in a safe place 3 Unscrew the retaining ring with its rubber O ring seal from the seal off flange 4 Tip the flange and let the viewing window fall into your hand 5 Insert either side of the new 122037 Quartz Viewing Window into the window aperture 6 Screw the retaining ring with O ring seal into the seal off flange and tighten securely 7 Clean ...

Page 12: ...DETECTOR Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 65 0267 09 JPG Rev 01 13 Printed in United States ...