background image

BA300 - Backflow Preventer

2

Product Specification Sheet • EN0H-1242GE23 R1117 • Subject to change

CONSTRUCTION

METHOD OF OPERATION

BA type backflow preventers are divided into three pressure 
zones. The pressure in zone

is higher than in zone 

which in turn is higher than in zone 

. A discharge valve is 

connected to zone 

 which opens at the latest when the 

differential pressure between zones 

 and 

 drops to 

0.14 bar. The water from zone 

 discharges to atmosphere, 

both check valves close and therefore separate zone 

from 

zone 

and 

. In this way the danger of back pressure or 

back syphonage into the supply network is prevented. The 
pipework connection is interrupted and the drinking water 
network is protected.

TRANSPORTATION AND STORAGE

Keep parts in their original packaging and unpack them 
shortly before use.

The following parameters apply during transportation and 
storage:

*non condensing

INSTALLATION GUIDELINES

Setup requirements

Install shut-off valves before and after backflow 
preventer

Install backflow preventer downstream of the filter or 
strainer

This protects the appliance against dirt

Install in horizontal pipework with the discharge valve 
downwards

Ensure good access

Simplifies maintenance and inspection

In order to avoid flooding, it is recommended to arrange 
a permanent, professionally dimensioned wastewater 
connection

The installation environment should be protected 
against frost and ventilated well

Install discharge pipework which has adequate capacity

These armatures need to be maintained regularly

Overview

Components

Materials

1

Three ball valves for the 
connection of a differential 
pressure gauge

Brass

2

Inlet/Outlet check valves

Stainless Steel

3

Housing

Ductile iron, powder-coated 
with polyamide

4

Discharge valve

CW626N with stainless steel 
seat

5

Pressure control line

Polyethylene with stainless 
steel braid

(BA300-80ZVDS stainless 
steel)

Not depicted components:

Diaphragm

EPDM

Sealing washers

EPDM

Parameter

Value

Environment: 

clean, dry and dust free

Min. ambient temperature: 

5 °C

Max. ambient temperature: 

55 °C

Min. ambient relative 
humidity: 

25 % *

Max. ambient relative 
humidity:

85 % *

Summary of Contents for BA300 Series

Page 1: ...L FEATURES Optimal protection of the drinking water supply system Easy access to all internal components Powder coated inside and outside Powder used is physiologically and toxicologically safe Easy Maintenance due to optimized construction Triple security two check valves and a discharge valve separate the backflow preventer into three pressure zones Few individual parts Light weight Standardised...

Page 2: ...ore and after backflow preventer Install backflow preventer downstream of the filter or strainer This protects the appliance against dirt Install in horizontal pipework with the discharge valve downwards Ensure good access Simplifies maintenance and inspection In order to avoid flooding it is recommended to arrange a permanent professionally dimensioned wastewater connection The installation envir...

Page 3: ... rate and the used connection size Connection sizes DN 65 80 100 150 200 inch 21 2 3 4 6 8 Min clearance above backflow preventer 650 mm 650 mm 650 mm 650 mm 650 mm Clearance from wall 160 mm 160 mm 160 mm 200 mm 200 mm 0 0 1 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 DN65 Flow V m3 h Pressure drop in valve Δp bar 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 1 1 2 1 3 1 4 1 5 1 6...

Page 4: ...er for connection size Accessories Overview F Parameter Values Connection size DN 65 80 100 150 200 Weight kg 23 9 32 7 44 6 70 9 114 1 Dimensions L 356 440 530 630 763 H 152 167 185 219 254 h 246 275 296 314 346 T 77 77 77 77 77 F 185 200 220 285 340 Nominal flow rate at Δp 1 0 bar m3 h 35 8 54 3 108 190 9 339 3 Discharge flow rates in the event of failure m3 h 35 35 35 35 35 BA300 A BA300 80ZVDS...

Page 5: ...ntrol line DN65 0904063 DN80 0904064 DN80 0904073 DN100 0904065 DN150 0904066 DN200 0904067 5 Sealing set DN65 0904068 DN80 0904069 DN100 0904070 DN150 0904071 DN200 0904072 Environmental Energy Solutions Honeywell GmbH Hardhofweg 74821 MOSBACH GERMANY Phone 49 6261 810 Fax 49 6261 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Divisio...