background image

BA300 - Backflow Preventer

4

Product Specification Sheet • EN0H-1242GE23 R1117 • Subject to change

DIMENSIONS

Note: 

 1 to 3 see chapter Method of operation

Note: 

 All dimensions in mm unless stated otherwise.

Note: 

 * F = width

ORDERING INFORMATION

The following tables contain all the information you need to make an order of an item of your choice. When ordering, please 
always state the type, the ordering or the part number.

Options

These backflow preventers are available in the following sizes: DN65, DN80, DN100, DN150, DN200.

• standard

- not available

Note: 

 ... = space holder for connection size

Accessories

Overview

F

Parameter

Values

Connection size:: 

DN

65 

80 

100 

150 

200 

Weight: 

kg

23.9 

32.7 

44.6 

70.9 

114.1 

Dimensions: 

L

356 

440 

530 

630 

763 

H

152 

167 

185 

219 

254 

h

246 

275 

296 

314 

346 

T

77 

77 

77 

77 

77 

F*

185 

200 

220 

285 

340 

Nominal flow rate at 

Δ

p = 1.0 bar: 

m

3

/h

35.8 

54.3 

108 

190.9 

339.3 

Discharge flow rates in the event of failure: 

m

3

/h

35 

35 

35 

35 

35 

BA300-...A

BA300-80ZVDS

Connection type: 

Standard version, connection sizes DN65 - DN200
Connection with flanges, PN10 

• 

with VdS certificate VdS No.: G417057 DN80 

• 

Description

Dimension

Part No.

TKA295

Test kit

Analogue pressure measuring device with differential pressure display. With case 
and accessories, ideal for inspection and maintenance of backflow preventer type 
BA.

TKA295

Summary of Contents for BA300 Series

Page 1: ...L FEATURES Optimal protection of the drinking water supply system Easy access to all internal components Powder coated inside and outside Powder used is physiologically and toxicologically safe Easy Maintenance due to optimized construction Triple security two check valves and a discharge valve separate the backflow preventer into three pressure zones Few individual parts Light weight Standardised...

Page 2: ...ore and after backflow preventer Install backflow preventer downstream of the filter or strainer This protects the appliance against dirt Install in horizontal pipework with the discharge valve downwards Ensure good access Simplifies maintenance and inspection In order to avoid flooding it is recommended to arrange a permanent professionally dimensioned wastewater connection The installation envir...

Page 3: ... rate and the used connection size Connection sizes DN 65 80 100 150 200 inch 21 2 3 4 6 8 Min clearance above backflow preventer 650 mm 650 mm 650 mm 650 mm 650 mm Clearance from wall 160 mm 160 mm 160 mm 200 mm 200 mm 0 0 1 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 DN65 Flow V m3 h Pressure drop in valve Δp bar 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 1 1 2 1 3 1 4 1 5 1 6...

Page 4: ...er for connection size Accessories Overview F Parameter Values Connection size DN 65 80 100 150 200 Weight kg 23 9 32 7 44 6 70 9 114 1 Dimensions L 356 440 530 630 763 H 152 167 185 219 254 h 246 275 296 314 346 T 77 77 77 77 77 F 185 200 220 285 340 Nominal flow rate at Δp 1 0 bar m3 h 35 8 54 3 108 190 9 339 3 Discharge flow rates in the event of failure m3 h 35 35 35 35 35 BA300 A BA300 80ZVDS...

Page 5: ...ntrol line DN65 0904063 DN80 0904064 DN80 0904073 DN100 0904065 DN150 0904066 DN200 0904067 5 Sealing set DN65 0904068 DN80 0904069 DN100 0904070 DN150 0904071 DN200 0904072 Environmental Energy Solutions Honeywell GmbH Hardhofweg 74821 MOSBACH GERMANY Phone 49 6261 810 Fax 49 6261 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Divisio...

Reviews: