background image

69-1085

2

CT2700 AN ELECTRONIC ROUND

 

 PROGRAMMABLE THERMOSTAT

Table 1. Compatibility Chart

Acquire tools and items as needed. See Fig. 1.

M878B

CROSS-RECESSED
SCREWDRIVER

HAND OR POWER
DRILL WITH 3/16 INCH
DRILL BIT, IF NEEDED TO
DRILL HOLES IN WALL

WIRE CUTTER/STRIPPER OR SHARP
KNIFE, IF NEEDED TO STRIP WIRES

MASKING TAPE, IF 
NEEDED TO LABEL WIRES 
AS DISCONNECTED FROM
OLD THERMOSTAT

LEVEL, IF NEEDED TO LEVEL
THERMOSTAT FOR APPEARANCE

Fig. 1. Required installation tools/supplies.

REMOVE OLD THERMOSTAT

Test to make certain that your heating and air
conditioning systems (where applicable) are working

properly. If either does not work, contact your local
heating/air conditioning dealer. To avoid compressor
damage, do n

ot

 operate the cooling system when outdoor

temperature is below 50

°

F (10

°

C).

CAUTION

Be careful when handling wires during
installation.
Damage to heating/cooling system possible.

Disconnect power at furnace or at main breaker/
fuse box before starting operation.

Carefully unpack your new thermostat, wallplate,
and decorator cover plate; save package of screws,

instructions and receipt.

Remove the cover from the old thermostat. If it does
not snap off when pulled firmly from the bottom,

check for a screw used to lock on the cover.

Loosen screws holding thermostat to subbase,
wallplate, to wall and lift away.

Disconnect wires from old thermostat or subbase.
As you disconnect each wire, use masking tape to

label it with the old terminal designation. If there are only
two wires, they do not need labeling. Wrap wires around a
pencil to keep them from falling back into the wall as
shown in Fig. 2.

WIRES THROUGH
WALL OPENING

M5136

Fig. 2. Wrapping wires around pencil.

Replacing Clock With C or C1
Clock Terminals

If you are replacing a Honeywell Chronotherm® Thermo-
stat, you may find one or two wires that go to the C or C1
clock terminals on the Chronotherm®

 

Thermostat wiring

wallplate. Do not allow them to touch, or you can damage
your transformer. Disconnect the wires and wrap them
separately using electrical tape; do not wrap them
together. Place the wires to avoid interfering with the new
thermostat operation. Record the colors and terminal
designation labels of the remaining wires.

Six or More Wires

If there are six or more wires connected to the thermostat
(excluding clock wires attached to terminals), you probably
have a variation of a multistage heat pump or other
multistage system. The thermostat is not compatible with
such systems so return the product to your retailer. If you
would like information about which programmable
thermostats work with your system, call Honeywell
Customer Assistance Center at 1-800-468-1502.

System Type

Compatible With CT2700

Gas—Standing Pilot

Yes

a

Gas—Electronic Ignition

Yes

Gas-Fired Boilers

Yes

a,b

Gas—Millivolt

No

Oil-Fired Boilers

Yes

b

Oil-Fired Furnace

Yes

Electric Furnace

Yes

Electric Air Conditioning

Yes

Baseboard Electric (120/240 Line Volt)

No

Heat Pumps/Multistage Equipment

No

Not compatible with any 120/240 volt circuit.
Not compatible with 2-wire White-Rodgers no. 1361 zone valves.

a

Not compatible with millivolt systems.

b

Compatible with 2-wire Honeywell zone valves. Isolating relay required for 3-wire thermostats zone valves

Summary of Contents for An Electronic Round CT2700

Page 1: ...ructions in this manual Direct any questions concerning the application of this thermostat to Honeywell Customer Assistance at 1 800 468 1502 Monday Friday 7 00 a m 5 30 p m Central time RECYCLING THERMOSTAT If this thermostat is replacing a control that contains mercury in a sealed tube do not place your old control in the trash Contact your local waste management authority for instructions regar...

Page 2: ...t need labeling Wrap wires around a pencil to keep them from falling back into the wall as shown in Fig 2 WIRES THROUGH WALL OPENING M5136 Fig 2 Wrapping wires around pencil Replacing Clock With C or C1 Clock Terminals If you are replacing a Honeywell Chronotherm Thermo stat you may find one or two wires that go to the C or C1 clock terminals on the Chronotherm Thermostat wiring wallplate Do not a...

Page 3: ...s plaster or wood drill 7 32 inch holes Gently tap provided anchors into the drilled holes until flush with the wall Reposition the decorator cover plate and wallplate pulling wires through the wiring opening Loosely insert the mounting screws into the holes Level for appearance only the thermostat functions properly even when not level Tighten the mounting screws 4 WIRE WALLPLATE TERMINALS The CT...

Page 4: ...s See Fig 8 Tighten the terminals M12537 FOR WRAPAROUND STRIP 7 16 INCHES 11 mm FOR STRAIGHT INSERTION STRIP 5 16 INCHES 8 mm Fig 8 CT2700 methods for wiring connection Plug the hole in the wall with insulation to help prevent drafts from adversely affecting thermostat operation 5 ADJUST FAN OPERATION SWITCH The thermostat fan operation switch labeled fuel switch in Fig 9 is set at the factory in ...

Page 5: ...the cooling temperature settings NOTE To exit the sequence at any time press until End is displayed 1 Set Current Time a Press b Press or to set current time If you wish to change the preprogrammed time tempera ture settings follow steps 2 through 6 If not press the key until End is displayed or the thermostat will automatically return to normal operational mode within five minutes 2 Set WAKE Time...

Page 6: ... to raise the temperature setting above the room temperature The cooling equipment should shut down Fan Slide the System switch to OFF and the Fan switch to ON The fan should run continuously CUSTOMIZE YOUR THERMOSTAT The following instructions provide the information neces sary to change the heating cycle rate to match your heating equipment choose Fahrenheit F or Celsius C and 12 or 24 hour cloc...

Page 7: ...eat gravity 1 Symptom Possible Cause Corrective Action Heating cooling equipment will not operate No AC power to thermostat Check power to heating cooling equipment On Off switch Fuse or circuit breaker Loose 24V connection At thermostat at furnace air conditioner Incorrect wiring check appropriate wiring diagram Thermostat inoperative See checkout section System switch on thermostat in wrong posi...

Page 8: ...mer Honeywell s sole responsibility shall be to repair or replace the product within the terms stated above Honeywell shall not be liable for any loss or damage of any kind including any incidental or consequential damages resulting directly or indirectly from any breach of any warranty expressed or implied or any other failure of this product Some states do not allow the exclusion or limitation o...

Reviews: