GSMHS Installation and Setup Guide
2-4
COMMUNICATIONS
MODULE
TRIGGERING DEVICE
GSMHS-001-V0
GND
GND
ZONE INPUT Z1/Z2
2
1
4
5
TB1
TRANSFORMER
AC INPUT 2
AC INPUT 1
+ TRIGGER
(VOLTAGE: 6-12V)
J1
BATTERY
Figure 2-3. Wiring the GSMHS Zone 1 Input for a Positive (+) Trigger
TRIGGERING DEVICE
iGSMBR-008-V0
GND
GND
ZONE INPUT Z1/Z2
2
1
4
5
TB1
TRANSFORMER
AC INPUT 2
AC INPUT 1
-
TRIGGER
(VOLTAGE: 0-1V)
NOTE:
TRIGGER VOLTAGE
IS +V TO GROUND FALLING
EDGE TRIGGER
COMMUNICATIONS
MODULE
J1
BATTERY
Figure 2-4. Wiring the GSMHS Zone 1 Input for a Ground (-V) Trigger
iGSMBR-010-V0
GND
ZONE INPUT Z1/Z2
2
1
4
5
TB1
TRANSFORMER
AC
AC
2K EOL
RESISTOR
N.C.
N.O.
COMMUNICATIONS
MODULE
J1
BATTERY
Figure 2-5. Wiring the GSMHS Zone 1 Input for EOL Supervised N.O./N.C. Triggers
UL
Zones should use EOL resistors, and be programmed as V+ Inverted or V– Inverted operation
such that a cut line results in an alarm.
Do not use zones 1 and 2 for UL installations.
Summary of Contents for AlarmNet GSMHS
Page 2: ......
Page 8: ...GSMHS Installation and Setup Guide 1 4 ...
Page 32: ...GSMHS Installation and Setup Guide 3 18 ...
Page 36: ...GSMHS Installation and Setup Guide 4 4 ...
Page 46: ...GSMHS Installation and Setup Guide B 2 ...
Page 48: ...GSMHS Installation and Setup Guide C 2 ...
Page 50: ...GSMHS Installation and Setup Guide D 2 ...
Page 51: ...NOTES ...
Page 52: ...NOTES ...
Page 53: ...NOTES ...