
∗∗∗∗
55
Dynamic Signaling Priority /
AAV Path Select (continued)
For AAV Path Select:
•
If using the UVS system or AVS system with non-ECP connection,
option 0 must always be used.
•
If using the AVS system with ECP connection, either option (0 or 1)
may be used, but note the following:
IMPORTANT:
If option “1” is selected, a 2-way voice (AAV) device
compatible with the communication device path must be used (ex.
GSMV communicator). When selected, AAV sessions
always
occur
via the GSMV communicator, even if reporting reverts to phone line
backup due to GSMV communicator path reporting failure.
∗∗∗∗
56
,
∗∗∗∗
57
,
∗∗∗∗
58
Menu Modes
These are Menu Mode commands, not data fields, for Zone Programming, Function Key Programming, and Expert Mode
Zone Programming respectively. See page 3 and respective sections later in this document.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (
∗∗∗∗
59 thru
∗∗∗∗
68, *70 thru
∗∗∗∗
76, and
∗∗∗∗
89):
For 3+1 or 4+1 Standard Format:
Enter a code in the
first box:
1–9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
A 0 (
not #+10) in the first box disables a report. A 0 (not #+10) in the second box results in advance to the next field.
For Expanded or 4+2 Format:
Enter codes in
both boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
A 0 (
not #+10) in the second box will eliminate the expanded message for that report. A 0 (not #+10) in both boxes will disable
the report.
For Ademco Contact ID® Reporting:
Enter any digit (other than 0) in the
first box, to enable zone to report (entries in the
second boxes are ignored).A 0 (not #+10) in the first box disables the report.
UL: Report codes are required in fields *61, *65, *71, *72, for UL Commercial Burglar Alarm installations.
Report codes are required in fields *60, *62, *63, *64, *70, *73, *74, *75, *76, for UL Commercial Burglar Alarm installations and required for
Residential Fire Alarm installations
SYSTEM STATUS REPORT CODES
(
✱
59–
✱
68)
∗∗∗∗
59
Exit Error Alarm Report Code
See above for entries.
V20PSIA/V15PSIA:
[1] Always enabled.
[0]
After arming the system, entry/exit and interior zones remaining open
after exit delay expires cause an alarm sound at the keypad and
external sounder (keypad also displays “EXIT ALARM”), and entry
delay begins. Disarming before the end of the entry delay stops the
alarm sounding and no message is sent to the central station. Keypad
displays “CA” (fixed-word) or “ALARM CANCELED” (alpha display).
If the system is not disarmed before entry delay expires, an “EXIT
ALARM” message (
V20PSIA/V15PSIA:
also zone alarm message) will
be sent to the central station. The keypad will display “EA” (fixed-word )
or “EXIT ALARM” (alpha display), and alarm sounding continues until
the system is disarmed (or timeout occurs).
An Exit Alarm condition will also result if a fault occurs in an exit or
interior zone within 2 minutes following the end of the exit delay, and an
“EXIT ALARM” message will be sent to the central station (except for
V20PSIA/V15PSIA
, see field *69 Recent Closing report). With Contact
ID format, the message will contain the zone number and error code
374 (“ALARM–EXIT ERROR”).
∗∗∗∗
60
Trouble Report Code
See above for entries.
|
[10] See UL System Reporting Note above *59.
Sent if a zone has a trouble condition.
∗∗∗∗
61
Bypass Report Code
See above for entries.
|
[00] See UL System Reporting Note above *59.
Sent when a zone is manually bypassed.
∗∗∗∗
62
AC Loss Report Code
See above for entries.
|
[10] See UL System Reporting Note above *59.
Timing of this report is random with up to a 4-hour delay. If AC restores
before the report goes out, there is no “AC LOSS” report.
∗∗∗∗
63
Low Bat Report Code
See above for entries.
|
[10] See UL System Reporting Note above *59
Sent when the system’s backup battery has a low-battery condition.
∗∗∗∗
64
Test Report Code
See above for entries.
Periodic Test Report Schedule Commands:
installer code +[#] + [0] + 0 = report every 24
hrs
installer code +[#] + [0] + 1 = report once per
week
installer code +[#] + [0] + 2 = report every 28
days
|
[00] See System Reporting UL Note above *59.
Sent periodically to test the communicator and phone lines.
Frequency of report is set in Scheduling mode (event 11) or by the key
commands listed at left:
Each mode sets schedule 32 (VISTA-20P) or schedule 08 (VISTA-15P)
to the stated repeat option; first test report sent 12 hours after
command.
†
† NOTE:
Make sure the Real-Time Clock is set to the proper time
before
entering the test report schedule command to ensure that test reports are sent
when expected. (see Setting the Real-Time Clock section)
–
9
–