38
Confirmation Of Arming Ding
0 = no
1 = yes (wired keypads and RF)
2 = yes, RF only (except 5827,
5827BD)
[0,0]
Part. 1
Part. 2
Confirmation of arming is 1/2-sec external sounder “ding.”
If 1 selected, ding occurs when closing report is sent if open/close
reporting is enabled, or at the end of Exit Delay. If 2 selected, ding
occurs upon reception of the wireless arming command.
UL: must be 1 for UL Commercial Burglar Alarm inst.
∗∗∗∗
39
Power Up In Previous State
0 = no, always power up disarmed;
1 = yes, power up in previous state
V20PSIA/V15PSIA:
Feature always
enabled; field does not exist.
When the system powers up armed, an alarm will occur 1 minute after
arming if a zone is faulted. Note that if the previous state was armed
Away or Stay, the system ignores sensor changes for 1 minute, which
allows sensors such as PIRs to stabilize.
UL: must be 1
SIA Guidelines: must be 1
DIALER PROGRAMMING (
✱
40 –
✱
42)
Do not fill unused spaces. Enter 0–9; #+11 for '
✱
'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum
digits entered, exit the field by pressing [
∗
]. The next data field number is displayed.
∗∗∗∗
40
PABX Access Code or Call
Waiting Disable
Enter up to 6 digits.
To clear entries, press
✱
40
✱
.
If call waiting is used, enter call waiting
disable digits “
∗
(#+11) 70” plus “# +
13” (pause).
V20PSIA/V15PSIA:
If call waiting is
used, enter call waiting disable digits
as described above, and also set Call
Waiting Disable option in field *91.
| | | | |
Call Waiting:
If the subscriber’s phone service has “call waiting” (and
is not using PABX), enter “*70” (“# + 11”) plus “# + 13” (pause) as the
PABX entry to disable “call waiting” during control panel calls. If the
subscriber does not have “call waiting” and is not using PABX, make
no entry in this field.
NOTES:
1. The call waiting disable feature cannot be used on a PABX line.
2. Using Call Waiting Disable on a non-call waiting line will prevent
successful communication to the central station.
∗∗∗∗
41
∗∗∗∗
42
Primary Phone No.
Secondary Phone No.
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press
✱
41
✱
or
✱
42
✱
respectively.
Enter the respective phone numbers.
∗∗∗∗
43
∗∗∗∗
44
∗∗∗∗
45
∗∗∗∗
46
Partition 1 Primary Acct. No.
Part. 1 Secondary Acct. No.
Partition 2 Primary Acct. No.
Partition 2 Secondary Acct. No.
Enter 4 or 10 digits, as chosen in *48
Report Format. Enter digits 0–9; #+11
for B; #+12 for C; #+13 for D; #+14 for
E; #+15 for F.
| | | / | | | | |
[FFFFFFFFFF]
| | | / | | | | |
[FFFFFFFFFF]
| | | / | | | | |
[FFFFFFFFFF]
| | | / | | | | |
[FFFFFFFFFF]
Enter [
∗
] as the fourth digit if a 3-digit account number (for 3+1 dialer
reporting format) is used. Enter 0 as the first digit of a 4-digit account
no. for 0000-0999. E.g., For Acct.
B234
, enter: #+11 + 2 + 3 + 4
To clear entries in a given field, press *43*, *44*, *45*, or *46* based
on the field being programmed
∗∗∗∗
47
Phone System Select
If Cent. Sta.
is not
on a WATS line:
0=Pulse Dial; 1=Tone Dial
If Cent. Sta.
is
on
a WATS line:
2 = Pulse Dial; 3 = Tone Dial
[1]
Select the type of phone service for the installation.
∗∗∗∗
48
Report F
ormat
0 = 3+1, 4+1 ADEMCO L/S STANDARD
1 = 3+1, 4+1 RADIONICS STANDARD;
2 = 4+2 ADEMCO L/S STAND.
3 = 4+2 RADIONICS STANDARD
5 = 10-digit ADEMCO CONTACT ID®
REPORTING
6 = 4+2 ADEMCO EXPRESS
7 = 4-digit ADEMCO CONTACT ID®
REPORTING
8 = 3+1, 4+1 ADEMCO L/S EXP.;
9 = 3+1, 4+1 RADIONICS EXP
[77]
primary
secondary
Select the format for primary/secondary phone numbers
–
7
–