Honeywell ADEMCO VISTA SERIES Programming Manual Download Page 34

∗∗∗∗

29 COMMUNICATION DEVICE MENU MODE 

(Pass-Through Programming) 

This mode is for programming an IP, GSM, or IP/GSM Communicator Module using an alpha keypad. Alternatively, these 

options can be programmed via the AlarmNet Direct website. After programming is complete, the module must be registered 

with AlarmNet before reporting via the communication device can occur. Refer to the device

s instructions for registration 

procedures.  

 

NOTE:

 The module must be set to device address 3. 

 

IMPORTANT: 

The use of an IP/GSM Communicator Module 

requires  an  AlarmNet

I  account.  Please  obtain  the  account 

information from the central station prior to programming this 

module.  

 

Using an Alpha Keypad as a 7720P Programming Tool 

When programming with 

29 menu mode, the alpha 

keypad mimics the functions of the 7720P Programming 

Tool. See figure to right and table below for 7720P key 

functions. Each key has two possible functions: a normal 

function and a SHIFT function.   

 

 

Normal functions:

 The numeric values labeled directly 

on the keys and the left-hand functions shown in 

diagram on the ABC keys. To perform a normal key 

function, simply press the desired key.  

 

 

SHIFT functions:

 Those functions shown in diagram 

above the numerical keys and the right-hand functions 

shown on the ABC keys. To perform a SHIFT key 

function, press SHIFT key (D key), then press the 

desired function key (shift function is indicated by the lit 

READY LED).  

 

1

OFF

4

MAX

7

INSTANT

READY

2

AWAY

5

TEST

8

CODE

0

3

STAY

6

BYPASS

9

CHIME

(B)

A

D

S

ENTER

SHIFT

N / Y

/

BS/ESC

SPACE

B

E

T

C

F

X

#

ARMED

READY

6160-7720P-001-V0

SHIFT

FUNCTION

WHEN LIT

(C)

(D)

(A)

 

7720P Emulation Template for Alpha Keypads

 

 

 

∗∗∗∗

29 IP/GSM Program Mode 

Press 

29 while in Data Field Programming mode. The following prompts appear. 

 

 

 

E NA B L E   I P / G S M?  
0 = N o ,   1 = Y e s  

 

Enable IP/GSM? 

0 = no, not using IP or GSM; 

1 = yes using IP and/or 

GSM module  

[

] to continue 

 

[Default = 0 (no IP and/or GSM)] 

If using a communication device, enter 1 at this prompt and 

enter 1-Prog at the next prompt to program the device. Use the 

communication device

s Installation Guide for details of the 

device

s programming prompts and instructions for registration. 

 

Fixed-Word Keypad Note:

 Although programming IP/GSM 

options cannot be done via a fixed-word keypad, IP/GSM can be 

enabled by doing the following:  
Enter 

∗∗∗∗

29

 (to enter IP/GSM menu mode), then press 

1 + [

∗∗∗∗

] + [

∗∗∗∗

 

 

 

1 = P RO G   2 = D I A G  
0 = Q U I T  

 

Programming /  

Diagnostics Select  

1= Prog (program the 

IP/GSM options) 

2 = Diag (diagnostic mode)  

0 = Quit; returns to data field 

programming mode 

Select whether you want to program the communication device 

or enter the device

s diagnostic mode. 

 

Diagnostic Mode Note: 

Diagnostic mode option available only 

for communicators with firmware version 2.4.16 or higher.

 

 

 

Normal and SHIFT key Functions While in 

∗∗∗∗

29 Menu Mode 

Key 

Normal Key Function 

SHIFT Key Function 

(A) = BS/ESC  [BS]: Press to delete entry 

[ESC]: Press to quit Program Mode 

 

Also, can reset EEPROM defaults 

 

 

(B) = 

/

 

[

]: Scroll down programming 

[

]: Scroll up programming  

(C) = N/Y 

[N]: Press for "NO" answer 

[Y]: Press SHIFT-Y for "YES" answer 

(D) = SHIFT 

Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a 

key is pressed. Press again for each SHIFT function desired. 

1/A 

[1]: For entering the number 1 

[A]: Used for entering C.S. ID number 

2/B 

[2]: For entering the number 2 

[B]: Used for entering C.S. ID number 

3/C 

[3]: For entering the number 3 

[C]: Used for entering C.S. ID number 

4/D 

[4]: For entering the number 4 

[D]: Used for entering C.S. ID number 

5/E 

[5]: For entering the number 5 

[E]: Used for entering C.S. ID number 

6/F 

[6]: For entering the number 6 

[F]: Used for entering C.S. ID number 

7/S 

[7]: For entering the number 7 

[S]: Press to display diagnostic status 

8/T 

[8]: For entering the number 8 

[T]: Press to send TEST messages 

9/X 

[9]: For entering the number 9 

[X]: Press to reset the IP/GSM  

[

] / SPACE 

[

]: Used to select programming options 

[SPACE]: Not used 

[0]: For entering the number 0 

 

[#] / ENTER 

[#] / ENTER: Press to accept entries 

No SHIFT function 

 

 

 

 

Active only when the "REVIEW?" prompt is displayed 

 

 34 

 

Summary of Contents for ADEMCO VISTA SERIES

Page 1: ...ADEMCO VISTA SERIES VISTA 20P VISTA 20PSIA VISTA 15P VISTA 15PSIA Security Systems Programming Guide K5305 1PRV8 5 11 Rev A ...

Page 2: ... the hallway outside may not wake up the sleeper if the door is closed DINING KITCHEN BEDROOM BEDROOM BEDROOM BEDROOM LIVING ROOM BEDROOM BDRM DINING LIVING ROOM TV ROOM KITCHEN BEDROOM BEDROOM TO BR LVNG RM BASEMENT KTCHN CLOSED DOOR GARAGE Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat Activated Detectors BDRM floor_plan 001 V1 Install a smoke detector insi...

Page 3: ...ANDS 33 SETTING THE REAL TIME CLOCK 33 29 COMMUNICATION DEVICE MENU MODE Pass Through Programming 34 UPLOADING DOWNLOADING VIA the INTERNET 35 ZONE TYPE DEFINITIONS 36 REPORT CODE FORMATS 37 SYSTEM SECURITY CODES 38 KEYPAD FUNCTIONS 39 VARIOUS SYSTEM TROUBLE DISPLAYS 40 UL NOTICES 41 SIA QUICK REFERENCE GUIDE 41 ULC S304 REQUIREMENTS for VISTA 15PCN and VISTA 20PCN 41 FCC STATEMENTS 42 LIMITATIONS...

Page 4: ...GSM options Exit Program Mode with installer code lockout Press 98 Exits programming mode and prevents re entry by Installer Code 8 0 0 To reenter programming mode the system must be powered down then powered up Then use method A above See field 88 for other 98 Program mode lockout options Exit Program Mode Press 99 Exits program mode and allows re entry by Installer Code 8 0 0 or method A above S...

Page 5: ... an RF jamming signal UL must be 1 if wireless devices are used 23 Quick Forced Bypass 0 no quick bypass 1 allow quick bypass code 6 0 0 Part 1 Part 2 Zones bypassed by this function will be displayed after the bypass is initiated UL must be 0 24 RF House ID Code 00 disable all wireless keypad use 01 31 using 5827 5827BD or 5804BD keypad 00 00 00 P1 P2 Common The House ID identifies receivers and ...

Page 6: ...e set for a minimum of 4 min option 1 for UL Commercial Burglary installations must be minimum 16 min option 4 34 Exit Delay 00 96 0 96 secs 97 120 secs V20PSIA V15PSIA 45 96 45 96 secs 97 120 secs NOTE Entries less than 45 will result in a 45 second delay 60 60 Part 1 Part 2 The system waits the time entered before arming entry exit zones If the entry exit door is left open after this time expire...

Page 7: ...ot using PABX enter 70 11 plus 13 pause as the PABX entry to disable call waiting during control panel calls If the subscriber does not have call waiting and is not using PABX make no entry in this field NOTES 1 The call waiting disable feature cannot be used on a PABX line 2 Using Call Waiting Disable on a non call waiting line will prevent successful communication to the central station 41 42 Pr...

Page 8: ...sent 1 15 secs 2 30 secs etc UL If using line security must be 0 Reports will be sent to both the dialer and the communication device 0 Select delay from 0 to 225 secs in 15 sec increments Intended for reporting via a communication device on the ECP bus LRR This field lets you select the time the panel should wait for acknowledgment from the first reporting destination see 55 before it attempts to...

Page 9: ...ounder keypad also displays EXIT ALARM and entry delay begins Disarming before the end of the entry delay stops the alarm sounding and no message is sent to the central station Keypad displays CA fixed word or ALARM CANCELED alpha display If the system is not disarmed before entry delay expires an EXIT ALARM message V20PSIA V15PSIA also zone alarm message will be sent to the central station The ke...

Page 10: ...RE REPORT CODES 70 76 70 Alarm Restore Rpt Code See above for entries 0 Alarm restore signals indicate that respective alarm zone s are no longer faulted Alarm restore reports are sent to the central station at bell timeout field 33 if the zone s in alarm are actually restored to a non faulted state at that time Otherwise alarm restore report s for respective alarm zones are sent when the system i...

Page 11: ...rify Keypad Display 0 no alarm canceled display 1 display Alarm Canceled when system is disarmed after an alarm has occurred To clear the ALARM CANCELED display the user must enter the security code OFF again 1 This feature causes a ALARM CANCELED display on the LCD keypad under the following conditions After the kissoff of the cancel message to the Central Station indicating a successful transmis...

Page 12: ...UL for AAV must use ADEMCO UVCM module or Honeywell AVS system Exit Delay Restart Reset must be disabled SIA Guidelines Exit Delay should be enabled Exit Delay Restart Reset option allows use of the key to restart the exit delay at any time when the system is armed STAY or INSTANT This feature also enables automatic exit delay reset which resets exit delay if the entry exit door is re opened and c...

Page 13: ...ypasses answer machine no no no 0 no yes no 0 no no yes 1 14 no yes yes 15 NOTE If 15 is entered to bypass an answering machine and a 4286 Phone Module is included in the system you should note the following When calling in from an off premises phone the user should make the initial call allow 1 or 2 rings only then hang up then call again The phone module will now seize the line and 2 long tones ...

Page 14: ...or zones entered in zone list 9 13 Alarms troubles for zones entered in zone list 9 and opens closes for all users 0 0 0 P1 P2 comm For each partition select from the listed options For users enabled for paging Reports to pager only when arming close disarming open from a keypad using a security code auto arming disarming arming with assigned button and keyswitch arming do not send pager messages ...

Page 15: ...ry 2 Faults on zones set for this option are cleared restore messages sent upon restoral of faults Vent Zone entry 2 Zones set for this option are ignored if faulted when arming the system but are protected if the zone is later restored e g an open window can be ignored when arming but if the window is later closed it will be protected opening the window again causes an alarm Bypass Disarmed entry...

Page 16: ...able 1 enable For Remote Services device usage 5 part 1 auto stay arm disabled Device Addresses Touchscreen device 1 Must set to 1 Touchscreen device 2 Must set to 2 Touchscreen device 3 Must set to 5 Touchscreen device 4 Must set to 6 1 1 0 0 AUI 1 AUI 2 AUI 3 AUI 4 System supports touchscreen style keypads e g Symphony Advanced User Interface and 6270 Touchscreen Keypad V20P up to 4 V15P up to 2...

Page 17: ...ield 190 for entries 0 0 Part Enable Sound 197 Exit Time Display Interval 0 no display 1 5 seconds between display refresh TOUCH SCREEN DEVICE NOTE If using more than one touch screen device e g 6270 Symphony with the system leave field 197 Exit Time Display Interval set to the default value 0 The 6270 automatically displays remaining exit time in one second increments 0 If enabled keypads display...

Page 18: ...faults when disarmed 3 never show any alarms trbles faults 0 no 4 power reset after fault by code OFF 12 verification see zone type 16 0 no 1 delay 1 2 delay 2 0 no 4 use exit delay 0 no 8 yes see note 2 Entry 7 fault display power reset verification Entry 8 entry delay 1 entry delay 2 exit delay interior zone type ENTRY 9 ENTRY 10 Alarm Sounds Use Bell Timeout Respond as Fire Zone Trouble Sounds ...

Page 19: ...ontinue This display appears upon entry into this mode The default is 0 No If 1 Yes is entered you will be prompted to confirm each transmitter after entering the serial and loop numbers at the XMIT TO CONFIRM prompt later Enter Zn Num 00 Quit 10 Zone Number VISTA 20P wired 01 08 and 09 48 wireless 09 48 RF button zones 49 64 VISTA 15P wired 01 06 and 07 22 wireless 09 34 RF button zones 49 56 Bot...

Page 20: ...battery signals The trans must stay within receiver s range UR Unsupervised RF Sends all the signals that the RF type does but the control does not supervise the check in signals The transmitter may therefore be carried off premises BR Unsupervised Button RF Sends only fault signals It will not send a low battery signal until it is activated The transmitter may be carried off premises NOTE For the...

Page 21: ... 0 no 1 yes to continue If you want to program descriptors for zones now enter 1 Yes and refer to the 82 Descriptor Programming section for available descriptors ENTER ZN NUM 00 QUIT 11 Next Zone Number to continue 00 quit If 0 No was entered above the system will return you to the ENTER ZN NUM prompt for the next zone When all zones have been programmed enter 00 to quit Completing Zone Programmin...

Page 22: ... number 1 6 see chart on next page See the defaults provided for each template in the chart that follows these procedures Select from templates Press to display template 1 shown selected NOTE If necessary press to back up and re enter template number Press if you want to return to 58 Menu mode summary screen L 01 02 03 04 T 23 22 21 23 Template Display When is pressed the selected template will be...

Page 23: ...prompt to enter the starting zone for the next wireless key Or you can return to 58 Menu mode by pressing 00 at the Zone Number prompt Wireless Key Predefined Default Templates 5834 013 V0 SERIAL 1 LOOP 4 SERIAL 1 LOOP 1 SERIAL 2 LOOP 1 SERIAL 2 LOOP 3 SERIAL 1 LOOP 3 SERIAL 2 LOOP 4 SERIAL 1 LOOP 2 SERIAL 2 LOOP 2 5834 4 Wireless Key Transmitter LOOP 4 5804 001 V4 LOOP 3 LOOP 1 LOOP 2 5804 Wirele...

Page 24: ...AY BYPASS A B C D keypad_keys 00 001 V0 Partition 1 Partition Number VISTA 20P 1 partition 1 2 partition 2 3 common partition to continue Enter the partition in which the function key is active Key A Func Zone 95 00 Define Key Function 00 12 see list at right to continue returns to key number prompt with the next function key letter displayed Enter the desired function for this key 00 to 12 from t...

Page 25: ...e the automated device action 79 RELAY POWERLINE CARRRIER DEVICE X 10 PROGRAMMING MENU MODE press 79 while in Programming mode The 79 Device Mapping Worksheet is on page 45 Use this menu to assign Relay Module device addresses and specific relay numbers and Powerline Carrier unit numbers The system is based on predefined module addresses for 4204 and 4229 modules Refer to the table shown at the Mo...

Page 26: ... 4204 option up to 4 events 2 4204 option up to 8 events 80 OUTPUT FUNCTION MENU MODE press 80 while in Programming mode The Output Definition Worksheet is on page 46 Use this mode to program output function definitions up to 48 functions that provide automated control of any of the output devices based on events occurring on individual zones or zones with certain zone types Each output definition...

Page 27: ...e Output Action prompt B 01 Enter Zn type Perimeter 03 Zone Type See list at right for available zone types prompt appears if zone type was selected Enter the desired zone type associated with this output number At the PARTITION prompt enter the partition in which this zone type will occur CHOICES FOR ZONE TYPES 00 Not Used 05 Day Night 12 Monitor Zone 01 Ent Exit 1 06 24 Hr Silent 14 Carbon Monox...

Page 28: ...eneral purpose V20PSIA V15PSIA dial delay disable 7 general purpose V20PSIA V15PSIA unlimited reports 8 general purpose 9 zones that activate Pager 1 10 zones that activate Pager 2 11 zones that activate Pager 3 VISTA 20P 12 zones that activate Pager 4 VISTA 20P Any list may include any or all of the system s zone numbers A zone list can be assigned to more than one output relay Zone List 4 When c...

Page 29: ...y List The phone module will not provide annunciation of any other words 82 Menu Mode Program Alpha 0 No 1 Yes 00 Program Alpha 0 no quit Alpha mode 1 yes to continue The Program Alpha prompt will appear Press 1 to continue Custom W ords 0 No 1 Yes 00 Custom Words 0 no 1 yes The Custom Words prompt will appear Press 0 to program standard alpha descriptors from the fixed vocabulary The system then ...

Page 30: ...for the second enter 02 etc A cursor will now appear at the beginning of the second line or 11 12 13 for partition 1 partition 2 and common lobby descriptors respectively See Assigning Partition Descriptors paragraph below NOTE Custom words 8 9 and 10 are reminder words that are programmed using Scheduling Mode 3 Refer to the Character List of letters numbers and symbols on a following page Press ...

Page 31: ...53 POWER R 155 RADIO 156 REAR 157 RECREATION 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF S 164 SAFE 165 SCREEN 166 SENSOR 167 SERVICE 168 SHED 169 SHOCK 170 SHOP 171 SHORT 173 SIDE 174 SKYLIGHT 175 SLIDING 176 SMOKE 178 SONS 179 SOUTH 180 SPRINKLER 182 STATION 184 STORE 185 STORAGE 186 STORY 190 SUPERVISED 191 SUPERVISION 192 SWIMMING 193 SWITCH T 194 TAMPER 196 TELCO 197 TELEPHONE 199 TE...

Page 32: ...st be enabled for paging see User Attributes in System Operation section Forced bypass is automatically enabled regardless of setting in field 23 If selected system displays custom words 8 9 and 10 at defined time Can be used as installer s reminder message to the end user See key commands in Test Report Code data field 64 section to quickly set periodic test reporting intervals NOTE Events 07 and...

Page 33: ...3 quick command installer code 0 6 remove all options set by 0 4 quick command Quick Program Command Results When either the 03 or 04 Quick Program command is used the following are automatically programmed and no longer available for other control panel purposes Pre Programmed 03 Command 04 Command Output Function No 80 mode VISTA 15P series 22 zone type 60 relay 07 23 zone type 61 relay 08 24 zo...

Page 34: ... or GSM If using a communication device enter 1 at this prompt and enter 1 Prog at the next prompt to program the device Use the communication device s Installation Guide for details of the device s programming prompts and instructions for registration Fixed Word Keypad Note Although programming IP GSM options cannot be done via a fixed word keypad IP GSM can be enabled by doing the following Ente...

Page 35: ...le s instructions for compatibility Compatible Modules 7845i ent supports LAN 7845i GSM 7845GSM GSMV System Requirements Internet Communication At the Installation Site Appropriate Internet Communication Module 7720P Programmer Broadband Internet Access for wired modules Broadband Cable DSL Modem for wired modules Broadband Cable DSL Router for wired modules if connecting more than one device to t...

Page 36: ...d in Night Stay mode zones assigned to zone list 05 night stay zone list are not bypassed when system armed in Night Stay mode Type 12 Monitor Zone Works as a dynamic monitor of a zone fault trouble not alarm In the case of a short open the message ALARM 24 Hr Non Burg XXX where XXX is the zone number will be sent to the Central Station The system keypad will display a check message indicating the...

Page 37: ... 00 ZZZ Zone contact ID number reporting the alarm or user number for open close reports System status messages contain zeroes in the ZZZ location TABLE OF CONTACT ID EVENT CODES Some event codes may not apply to certain control panels for a complete list of event codes refer to the central office receiver manual Code Definition 110 Fire Alarm 121 Duress 122 Alarm 24 hour Silent 123 Alarm 24 hour ...

Page 38: ...ity levels if desired any user can be assigned the partition master authority level 0 User 03 49 V20P 03 33 V15P perform security functions arm disarm etc only cannot add delete users view event log set system clock or program scheduled events 1 Arm Only see user arm system only 2 Guest see user can disarm the system only if it was used to arm the system 3 Duress see user performs security functio...

Page 39: ... Stay Arm feature is enabled field 84 and the entry exit door is not opened and closed within the programmed exit delay time the system will automatically arm in STAY mode if armed from a wired keypad non RF device If the door is opened and closed within the exit delay period the system arms in AWAY mode Arming Stay Enter code STAY 3 or simply press appropriate key on the keypads see Single Button...

Page 40: ...eless sensors contain a non replaceable long life battery which requires replacement of the entire unit at the end of battery life e g Nos 5802 5802CP TELCO FAULT 94 Telephone Line Failure indicates that a monitored telephone line if programmed in field 92 has been cut or disconnected Depending on how the system was programmed the keypad may also produce a trouble sound and the external sounder ma...

Page 41: ... Default is code enabled 10 69 Recent Closing Report Code Always enabled 11 91 Option Selection Exit Delay option should be enabled If call waiting is used Call Waiting Disable must be set to 1 enabled 12 93 No reports in Armed Period Must be set for 1 or 2 report pairs 13 Cross zone timer programming is set in field 85 cross zone pairs are assigned in zone list 4 using 81 Zone List mode 14 Duress...

Page 42: ...partment does not guarantee the equipment will operate to the user s satisfaction Before installing this equipment users should ensure that it is permissible to be connected to the facilities of the local telecommunications company The equipment must also be installed using an acceptable method of connection The customer should be aware that compliance with the above conditions may not prevent deg...

Page 43: ...hanges in temperature however as the ambient temperature of the protected area approaches the temperature range of 90 to 105 F 32 to 40 C the detection performance can decrease Alarm warning devices such as sirens bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors If warning devices are located on a different level of the re...

Page 44: ...R 58 1 BR 59 1 BR 60 1 BR 61 1 BR 62 1 BR 63 1 BR 64 1 BR 95 00 N A N A N A N A keypad 1 96 00 N A N A N A N A keypad 3 99 06 N A N A N A N A keypad Emergency key zones 95 96 and 99 report the partition of the keypad used to activate the emergency zones NOTES Zone Type see chart 56 Zone Programming Menu mode section Report Code enabled if first digit is a non zero number Hardwire Type zns 2 8 0 EO...

Page 45: ...UT TYPE OUTPUT TYPE 09 16 apply to VISTA 20P only Relay X10 Relay X10 Output No Module Addr Pos 1 4 Unit No Description Output No Module Addr Pos 1 4 Unit No Description 01 09 02 10 03 11 04 12 05 13 06 14 07 15 08 16 17 On Board Trigger 1 norm output 18 On Board Trigger 2 norm output WORKSHEET for 81 ZONE LIST PROGRAMMING Fill in the required data on the worksheet below and follow the procedure i...

Page 46: ...45 46 47 48 ZONE TYPE SYSTEM OPERATION Choices for Zone Types are 00 Not Used 05 Trouble Day Alarm Night 10 Interior w Delay 24 Silent Burglary 01 Entry Exit 1 06 24 Hr Silent 12 Monitor Zone 77 Keyswitch 02 Entry Exit 2 07 24 Hr Audible 14 Carbon Monoxide 81 AAV Monitor Zone 03 Perimeter 08 24 Hr Aux 16 Fire w Verification 90 91 Configurable 04 Interior Follower 09 Fire 23 No Alarm Response when ...

Page 47: ...4 104 automatic if phone module access code field 28 enabled Zone Expanders 4219 4229 module 1 for zones 09 16 module 2 for zones 17 24 module 3 for zones 25 32 module 4 for zones 33 40 module 5 for zones 41 48 07 08 09 V20P 10 V20P 11 V20P 107 108 109 110 111 56 zone programming input device type entry then automatic if zone no 9 16 entered as AW type or relay assigned automatic if zone no 17 24 ...

Page 48: ...NROLL AS RF 5819S WHS BRS ENROLL AS RF LOOP 1 INTERNAL SHOCK SENSOR LOOP 2 REED 5819 ENROLL AS RF LOOP 2 REED LOOP 3 TERMINALS LOOP 1 TERMINALS 5800WAVE PROGRAM HOUSE ID 5800PIR OD ENROLL AS RF 5800PIR 5800PIR COM ENROLL AS RF 5811 ENROLL AS RF 5800PIR RES ENROLL AS RF 5800Micra ENROLL AS RF 5800CO ENROLL AS RF 5800SS1 ENROLL AS RF LOOP 1 LOOP 1 LOW SENSITIVITY LOOP 2 HIGH SENSITIVITY LOOP 3 TEMP ...

Reviews: