Commissioning
Instruction manual 854 ATG
Page 19
Item
Name
Description
W2
=
Protection level 2
Enter protection level 2 (default password: ENRAF2)
TT
= Tank top
Format according to item
LD
. The tank top level must be set for
correct wire weight compensation. The value you enter now, is
overwritten when the level calibration with displacer stop is used.
MH
= Motor limit switch high
Format according to item
LD
. This is the highest allowed position for
the displacer during normal operation.
MZ
= Lock test limit switch level
Format according to item
LD
. Item
MZ
sets the highest displacer
position during a lock test.
ML
= Motor limit switch low
Format according to item
LD
. This is the lowest allowed position for
the displacer during normal operation.
DC
Drum circumference
Standard floating point format; units: metres.
Check whether the pre-programmed drum circumference is in
accordance with the engraved value of the installed measuring drum.
If that is not correct, enter the engraved drum circumference.
DW
Displacer weight
Standard floating point format; unit: grams. The standard displacers
have a weight of 223 g. If a density displacer is used, check whether
the engraved weight is programmed correctly in this item. If not, then
enter the engraved displacer weight.
DA
Displacer area
Standard floating point format; units: cm
2
.
Check whether the pre-programmed displacer area is in accordance
with the used type of displacer. Refer to Appendix B for information on
the displacer area values. If not correct, program the correct displacer
area.
S1
Set point
Standard floating point format; units: grams. With the standard
displacers, the interface 1 set point (level surface) is set to 208 g.
If a density displacer is used, program
S1
as: (
DW
- 15).
TA
= Transmission address
Two digits. The transmission address identifies the gauge on the
Honeywell Enraf 2-wire field bus. Each gauge must have a unique
address, and hence
TA
must be programmed differently. When
connected to an 858 CIU, please note that the 858 CIU has three
highways, containing the following transmission addresses:
CIU highway
Transmission address (
TA
)
TL 1
00 - 29
TL 2
30 - 59
TL 3
60 - 99
TI
=
Tank identifier
Six characters. Used as a label; the tank name can be programmed in
the tank identifier item (spaces are not allowed!).
TS
= Transmission speed
Four digits; either 1200 (default) or 2400. Units: baud
GT
= Gauge type
One character. Represents the gauge type. For the 854 ATG, GT=B.
EX
Exit
Exit protection level 2. The gauge will now initialize and after start-up,
the modified settings become active.
Summary of Contents for 854 ATG Series
Page 1: ...Instruction manual Series 854 ATG level gauge ...
Page 2: ......
Page 53: ...Appendix Instruction manual 854 ATG Page 51 ...
Page 55: ...Appendix Instruction manual 854 ATG Page 53 ...
Page 56: ...Appendix Page 54 Appendix C ASCII table ...
Page 58: ...Appendix Page 56 Level display format B Average gas temperature display format C ...
Page 60: ...Appendix Page 58 HIMS pressure displays format F and H Servo density display format I ...
Page 62: ...Appendix Page 60 Appendix E PCB layout XPU 2 HCU HCU SPU II GFC ...
Page 67: ......