5-16
MAN0448_Issue 13_ 01-2010
5704 Control System
005704-M-5001 A03249
CHAPTER 5 - COMMISSIONING AND
MAINTENANCE INSTRUCTIONS
5.5 System Errors
69
Invalid Sub-Channel
Indicates a request has been received for
an invalid sub-channel address.
68
Printer Not Ready
Indicates that the serial device attached to
the engineering port is not able to accept
data.
67
Invalid Request
Indicates that an invalid request number
has been received.
66
Serial Communications Timeout
Serial communications has timed out.
Reset card by removing power to the card.
If problem persists, replace the card.
65
Failed Error
Failed to receive command or card
selected.
Reset card by removing power to the card.
If problem persists, replace the card.
64
Timeout Error
Backplane command timed out.
Reset card by removing power to the card.
If problem persists, replace the card.
63
Slot Inactive Error
Backplane command sent to empty slot.
Reset card by removing power to the card.
If problem persists, replace the card.
Error
Error Code Meaning
Software Card Fault latch
Code
Version Status Signal
All
Active No
No
All
Active No
No
All
Active No
No
All
Active No
No
All
Active No
No
All
Active No
No
All
Active No
No
Summary of Contents for 5704
Page 1: ...System 57 5704 Control System Operating Instructions ...
Page 4: ...4 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 ...
Page 6: ...6 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...
Page 14: ...1 8 MAN0448_Issue 13_01 2010 5704 Control System 005704 M 5001 A03249 User Notes ...