Honeywell Sensing and Control

Limitless™ WLS Series 

Single Switch Adapter

ISSUE 1

  

 

50081314

This WLS Single Switch Adapter quick start installation guide provides basic installation instructions for the WLS Single Switch 
Adapter used in conjunction with a Limitless™ Wireless Panel Mount Monitor (WPMM) or a Limitless™ Wireless DIN Rail Receiver 
(WDRR).  If necessary, refer to the WLS, WDRR or WPMM Installation and Technical Manual for further detailed information regarding 
installation.

1.1 

Antenna Connection

m

 WARNING

RF EXPOSURE

To satisfy FCC RF exposure requirements for mobile transmitting devices, a separation distance of 20 cm [7.87 in] or more should 

be maintained between the antenna of this device and persons during device operation To ensure compliance, operation at closer 

than this distance is not recommended. The antenna used for this transmission must not be co-located in conjunction with any 

other antenna or transmitter.

Failure to comply with these instructions could result in death or serious injury.

CAUTION

Power to the WLS Single Switch Adapter should not be applied (ensure battery is removed) during installation of antenna as dam-
age could occur to the WLS Single Switch Adapter electronics.

The antenna and antenna guard are packaged separately and thus will need to be assembled to the WLS Single Switch 
Adapter.

direct mount antenna

 (either straight or tilt & swivel) can be easily mounted by threading the mating RP-SMA plug of the antenna 

to the RP-SMA jack on the WLS Single Switch Adapter. Tighten the connection until finger tight. Then, attach the antenna guard by 
simply threading the guard finger tight onto the threaded base with the RP-SMA connector.

remote mount antenna

 requires the use of an extension cable to allow the antenna to be mounted in a different location than the 

WLS Single Switch Adapter location. The extension cable will need to have one end with a RP-SMA plug connector which will mate 
with the WLS Single Switch Adapter connector jack under the same mounting procedure as the direct mount antenna. The other end 
of the extension cable will need to mate with antenna connector directly or it may be integral to the particular remote mount antenna 
chosen.

1.2   End User Switch Connection

A WLS Single Switch Adapter requires the use of an end-user supplied switch that is electrically connected to the WLS Single Switch 
Adapter. The switch design must be SPDT (Form C) low-energy contact design (i.e. gold contacts), capable of reliably controlling a 
30 mA @ 3.6 Vdc electrical load. The electrical connections are made using the M12 micro-connector supplied with the WLS Single 
Switch Adapter along with the end-user supplied connector with three-wire mating cable (see Figure 1 as an example). Another 
electrical connection option for the WLS Single Switch Adapter Series utilizes an end-user supplied three-wire electrical cable routed 
through a cable grip on the WLS Single Switch Adapter and connected to an internal electrical connector (see Figure 3 as an ex-
ample.).

Electrical connections:

  Special code BT1 or BT2 in the WLS Single Switch Adapter part number: User supplied connector with 

three-wire mating cable for use with WLS Single Switch Adapter M12 micro-connector. 

The user-supplied electrical connector/cable must mate with Molex p/n: 1200700056 (Brad Harrison p/n: 8R3A00A18A120).

Summary of Contents for 50081314

Page 1: ...r learning and meeting the required Declaration of Conformity Regulations Guidelines etc for each country in their distribution market m WARNING RF EXPOSURE To satisfy FCC RF exposure requirements for mobile transmitting devices a separation distance of 20 cm or more should be maintained between the antenna of this device and persons during device operation To ensure compliance operation at closer...

Page 2: ...ttach the antenna guard by simply threading the guard finger tight onto the threaded base with the RP SMA connector A remote mount antenna requires the use of an extension cable to allow the antenna to be mounted in a different location than the WLS Single Switch Adapter location The extension cable will need to have one end with a RP SMA plug connector which will mate with the WLS Single Switch A...

Page 3: ... common terminal of the user supplied switch BLACK wire Connect to normally open terminal of the user supplied switch BLUE wire Connect to normally closed terminal of the user supplied switch Figure 1 Limitless WLS Single Switch Adapter BT1 BT2 Conductor to Switch Step 2 Connect the mating connector w cable to the WLS Single Switch Adapter M12 connector and then tighten connector see Figure 2 Figu...

Page 4: ...ot tighten the cable grip at this time See Figure 3 page 4 2 Connect the three 3 user supplied wires to the user supplied switch terminal common normally open and normally closed See example in Figure 4 page 5 3 Connect the user supplied switch common normally open and normally closed wires to the same labeled internal con nector COM NO NC of the WLS Single Switch Adapter See example in Figure 5 p...

Page 5: ...ith these instructions could result in death or serious injury m WARNING RISK OF DEATH OR SERIOUS INJURY FROM EXPLOSION OR FIRE If WLS Single Switch Adapter is to be returned to Honeywell for any reason the battery MUST be removed prior to shipping Dispose of used batteries promptly per local regulations or the battery manufacturer s recommendations Keep away from children Do not disassemble and d...

Page 6: ...licable remove the two screws on the housing cover 2 Using a finger press down slightly on the battery top and remove the battery insulator Insure that the battery is prop erly seated and making good contact 3 Replace cover and retighten screws or immediately proceed to Section 1 4 Pairing Mode Figure 6 Limitless WLS Single Switch Adapter Hous ing Figure 7 Limitless WLS Single Switch Adapter Bat t...

Page 7: ...nderstand the timing of events that need to be performed 2 WLS Single Switch Adapter Remove if required the two screws on the housing cover See Figure 3 page 4 of the WLS Single Switch Adapter and locate the function button to be used in Step 4 3 WPMM Press the Function button on WPMM See Figure 4 page 5 for more than four seconds and less than eight seconds at which time the green and yellow LEDs...

Page 8: ...imitless WLS Single Switch Adapter Hous ing 1 1 Figure 10 Limitless WLS Single Switch Adapter with Function Button Depressed Figure 9 Limitless WPMM Housing NOTE Use a blunt object such as a paper clip to actuate the function switch Figure 11 Limitless WLS Single Switch Adapter Label Placement 7 7 8 6 6 ...

Page 9: ...iring mode 4 WLS Single Switch Adapter Within a 30 second interval of Step 3 depress the WLS Single Switch Adapter function button See Figure 10 page 8 and hold depressed for more than one second and less than 12 seconds at which time the orange LED turns on see Figure 10 page 8 While in pairing mode the orange LED will flash on for 100 ms every second The orange LED flashes three times 100 ms on ...

Page 10: ...10 Honeywell Sensing and Control Limitless WLS Series Single Switch Adapter ISSUE 1 50081314 Figure 12 Limitless WDRR Housing ...

Page 11: ... 1 4 WLS Single Switch Adapter Mounting Mounting The WLS Single Switch Adapter housing has two slotted mounting holes that will accept a M5 or 10 size screw and it also has two 10 32 UNF tapped holes for mounting from the back Figure 13 Limitless WLS Single Switch Adapter Mounting Hole Diagram ...

Page 12: ...r An acceptable RF signal is also indicated by the RF signal strength LEDs on the WDRR see the WDRR Installa tion and Technical Manual for further information Figure 14 Limitless WLS Single Switch Adapter and WPMM in Parallel m WARNING RF EXPOSURE To satisfy FCC RF exposure requirements for mobile transmitting devices a separation distance of 20 cm 7 87 in or more should be maintained between the ...

Page 13: ...e In no event shall Honeywell be liable for consequential special or indirect damages While we provide application assistance personally through our literature and the Honeywell web site it is up to the customer to determine the suitability of the product in the application Specifications may change without notice The information we supply is believed to be accurate and reliable as of this printin...

Reviews: