Precision Platform 4022 Scanner
System Testing and Verification
10/4/07
P/N
6510020208
4-18
1.
Measure the ambient temperature around the head while it is
onsheet. Take the measurement 30 cm (1 ft) above or below the
sheet and 60 cm (2 ft) in from the sheet edge.
2.
Test the results by performing several scans and observing whether
condensation forms on the guides.
3.
If necessary, readjust the controller settings and repeat steps 2 and
3 until the optimal temperature is achieved. See Table 4-2.
Table 4-2 Air Wipe Heater Controller Settings
Setting
Air Wipe Temperature Offsheet
1
Approx. 85
°
F (29
°
C)
2
Approx. 99
°
F (37
°
C)
3
Approx. 113
°
F (45
°
C)
4
Approx. 127
°
F (53
°
C)
5
Approx. 141
°
F (61
°
C)
6
Approx. 155
°
F (68
°
C)
7
Approx. 169
°
F (76
°
C)
8
Approx. 183
°
F (84
°
C)
9
Approx. 197
°
F (92
°
C)
10
Approx. 212
°
F (100
°
C)
Note that airwipe heaters are not present on the 4022-40 Wire Calender
Scanner heads.
4.5.3. Internal head air pressure
The head is continuously pressurized with air from a bleed valve on the
Environment Control Unit (ECU). This prevents water and condensate
from entering the head when reduced internal head temperature causes
pressures below ambient. If the pressure is too much, the basis weight
Kapton windows will bow into the gap. To reduce the pressure, reduce
the flow from the bleed valve. If the pressure is too low, the humidity
sensor in the head will read high and an alarm will be generated at the
operator station.
Summary of Contents for 4022
Page 1: ...Precision Platform 4022 Scanner System Manual 6510020208 ...
Page 2: ......
Page 3: ...Precision Platform 4022 Scanner October 2007 ...
Page 22: ......
Page 72: ......
Page 94: ......
Page 126: ......
Page 162: ......
Page 170: ......
Page 234: ......
Page 239: ...Glossary p n 6510020208 10 18 07 11 5 VIO Virtual Input Output ...