background image

393691 LP GAS AND 394588 NATURAL GAS CONVERSION KITS

69-0244EF—01

2

Fig. 2. Conversion kit installation in regulator. 

5.

Install the new plastic pressure regulator 
adjustment screw. Assure that the screw top is 
flush with the regulator top.

6.

Turn pressure regulator adjustment screw 
clockwise 

 eleven complete turns. The 

preliminary pressure setting is approximately 
10.0 in. wc (2.5 kPa) for LP gas regulator 
(393691) and 3.5 in. wc (0.9 kPa) for natural gas 
regulator (394588).

7.

Check the regulator setting using a manometer 
or by clocking the gas meter. See Check and 
Adjust Gas Input and Burner Ignition section.

8.

Install the new cap screw and O ring.

9.

Mount conversion label on the gas control.

10.

Install the gas control and appliance according 
to appliance manufacturer instructions.

START-UP

Gas Control Knob Settings

OFF: Prevents pilot and main burner gas flow.

PILOT (On standing pilot controls only): Permits 
pilot burner gas flow when red knob is held down or 
thermocouple current is above power unit dropout 
value.

ON: Permits gas flow into gas control. Pilot burner 
gas is controlled as in the PILOT position for stand-
ing pilot and intermittent pilot systems. Main 
burner gas flow is controlled by thermostat and 
automatic valve operators.

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard.

Can cause severe injury, death or property 

damage.

Check for gas leaks with soap and water 
solution any time work is done on a gas system.

Gas Leak Test

1.

Paint pipe connections upstream of gas control 
with rich soap and water solution. Bubbles indi-
cate gas leak.

2.

If gas leak is detected, tighten all pipe connec-
tions.

3.

Stand clear of main burner while lighting to pre-
vent injury caused from hidden leaks that could 
cause flashback in the appliance vestibule. Light 
main burner.

4.

With main burner operating, paint pipe joints 
(including adapters) and control inlet and outlet 
with rich soap and water solution. 

5.

If another gas leak is detected, tighten adapter 
screws, joints, and pipe connections.

6.

Replace part if gas leak can not be stopped.

Light Pilot (Standing Pilot 
Models)

1.

Turn gas control knob clockwise 

 to OFF. 

Wait five minutes to dissipate any unburned gas. 
Smell for gas around the appliance near the 
floor. Do not relight pilot flame if you smell gas.

2.

Turn gas control knob counterclockwise 

 

to PILOT. Push down and hold the knob while 
lighting the pilot flame.

3.

Hold down the gas control knob about one min-
ute, then release.
a. If pilot flame goes out, turn gas control knob 

clockwise  

to 

OFF 

and repeat steps 1 

through 3.

b. If pilot flame remains lit, turn gas control 

knob counterclockwise 

 to ON.

Turn on System (Intermittent and 
Direct Ignition Systems)

Rotate the gas control knob counterclockwise 

 to 

ON.

Turn on Main Burner

Follow appliance manufacturer instructions or adjust 
thermostat setting to call for heat.

Adjust Pilot Flame

The pilot flame should envelop 3/8 to 1/2 in. (10 to 13 
mm) of the thermocouple or igniter-sensor tip. Refer 
to Fig. 3. To adjust pilot flame:

1.

Remove pilot adjustment cap screw. Refer to 
Fig. 1. 

2.

Turn inner adjustment screw clockwise

 to 

decrease or counterclockwise 

 to increase 

pilot flame.

3.

Always replace cap screw after adjustment and 
tighten firmly to safeguard proper operation.

COLOR CODE FOR
LP

GAS

NATURAL

GAS

CAP SCREW BLACK

BLACK

BLACK

SILVER

PRESSURE

REGULATOR

ADJUSTING

SCREW

BLACK

BLACK

SPRING 

RED

STAINLESS

STEEL

PRESSURE

REGULATOR

HOUSING

M7780B

O RING             

Summary of Contents for 393691

Page 1: ...RNING Fire or Explosion Hazard Can cause severe injury death or property damage Follow these warnings exactly 1 Disconnect power supply before wiring to prevent electrical shock or equipment damage 2 To avoid dangerous accumulation of fuel gas turn off gas supply at appliance service valve before starting installation and perform Gas Leak Test after completion of installation 3 Use only your hand ...

Page 2: ...connec tions 3 Stand clear of main burner while lighting to pre vent injury caused from hidden leaks that could cause flashback in the appliance vestibule Light main burner 4 With main burner operating paint pipe joints including adapters and control inlet and outlet with rich soap and water solution 5 If another gas leak is detected tighten adapter screws joints and pipe connections 6 Replace par...

Page 3: ...e pressure regulator adjustment cap screw b Using a screwdriver turn inner adjustment screw clockwise to increase or counterclockwise to decrease gas pressure to main burner c Always replace cap screw and tighten firmly to prevent gas leakage 7 Turn gas control knob to PILOT standing pilot system or OFF intermittent and direct ignition systems 8 Remove pressure gauge and replace outlet pressure ta...

Page 4: ...at least one complete cycle to assure all con trols are operating properly 3 If manometer pressure gauge method is used perform Gas Leak Test at outlet pressure tap plug 4 Apply the conversion label in the conversion kit to the gas control heating appliance and any other controls to show conversion to a new type of gas Time sec Flow cfh Flow m3 hr 40 90 2 55 41 88 2 50 42 86 2 44 43 84 2 38 44 82 ...

Page 5: ... AVERTISSEMENT Risque d incendie ou d explosion Peut causer des blessures graves le décès ou des dommages matériels Suivez exactement ces avertissements 1 Débranchez l alimentation électrique avant d effectuer le câblage afin de prévenir les décharges électriques ou l endommagement de l équipement 2 Pour éviter l accumulation dangereuse de gaz combustible fermez la vanne d alimentation en gaz de l...

Page 6: ...st de fuite de gaz 1 Recouvrez les raccords de conduit au dessus de l appareil de contrôle du gaz avec une solution riche de savon et d eau Les bulles indiquent une fuite de gaz 2 Si une fuite de gaz est détectée serrez tous les raccords de conduit 3 Tenez vous à l écart du brûleur principal lors de l allumage pour prévenir des blessures causées par des fuites cachées qui pourraient entraîner un r...

Page 7: ...ion de la pression du gaz à l aide d un manomètre indicateur de pression 1 Tournez la molette de contrôle du gaz vers la position PILOT veilleuse systèmes à veilleuse permanente ou vers la position OFF arrêt systèmes à allumage intermittent et direct 2 Retirez le bouchon de prise de pression de sortie de l appareil de contrôle du gaz et branchez l indicateur de pression Consultez la Fig 1 3 Tourne...

Page 8: ...toujours la vis d assemblage et serrez la fermement pour prévenir les fuites de gaz 8 Rétablissez l alimentation en gaz vers les autres appareils en marche et rallumez toutes les flammes de veilleuse conformément aux instructions du fabricant 9 Passez à la section Vérification Tableau 1 Conversion du taux d écoulement du gaz VÉRIFICATION 1 Assurez vous que l alimentation en air vers le brûleur pri...

Reviews: