8. Troubleshooting
8.1. Error Code
196
2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide
R200
Honeywell
May 2010
Error code
(Dec)
Description
RUN LED
status
CH0 CH1
32
132 Compared output 1 maximum value exceeded maximum input
range
33
133 Compared output 1 minimum value > compared output1
maximum value set
34
134 Pulses per revolution range exceeded
35
135 Frequency input mode range exceeded
ATTENTION
•
If the module status is normal, RUN LED is ON.
•
If two or more errors occur, the module saves the first error code
generated. The displayed error is deleted first and then the next error is
displayed.
•
In case of fatal error where LED blinks every 0.2 sec., recycle the power
(OFF -> ON) to delete the error.
•
In case of non-fatal error where LED blinks every 1 sec., the error can be
removed without recycling the power (OFF -> ON) and the module can
keep operating.
•
In case of non-fatal error where LED blinks every 1 sec, the parameter
value causing the specific error is not set on the module, and the existing
parameter value is kept as it is.