2. Specifications
2.4. Main functions
R200
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
35
September 2010
Honeywell
If any isolated DA module error occurs
CPU Status
Output Status
Channel
Remarks
Run
Stop
RUN
Enabled
ATTENTION
0V or 0mA
0: previous
value kept
1: minimum
output
2: middle output
3: maximum
output
Disabled
As specified
setting output
type
0V or 0mA
STOP
Enabled
As specified
setting output
type
0V or 0mA
Disabled
As specified
setting output
type
0V or 0mA
When Power is on /H/W error
0V or 0mA
ATTENTION
•
Output value setting error
: upper limit or lower limit.
•
Parameter setting error
: as specified CH output type.
If any CPU error occurs
CPU Status
Output Status
Channel
Remarks
Run
Stop
ERROR
Enabled
0V or 0mA
Disabled
Display and diagnosis functions
1.
Run LED
: Displays the operation status of isolated D/A conversion module.
−
ON
: Operation normal
−
Blinks
: Error occurs (Refer to error status below)
−
Off
: DC 5V disconnected or module error