3. Installation and wiring
3.2. Installation
46
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
200
Honeywell
September 2010
Safety instructions for waste disposal
CAUTION
Product or battery waste will be processed as industrial waste. The
waste may discharge toxic materials or explode itself
.
3.2
Installation
Installation environment
The isolated D/A conversion module is designed to withstand extreme climatic
conditions. However, care must be taken for the following items to ensure reliability and
stability.
1.
Environmental conditions
−
Install on a waterproof and dustproof control panel.
−
Ensure that there is no continuous impact or vibration on the module.
−
Avoid exposure to direct sunlight.
−
Ensure that there is no dew formation caused by rapid change in temperature.
−
Ensure an ambient temperature of 0-55°.
2.
Installation
−
Ensure that wiring waste does not get inside PLC when wiring or drilling screw
holes.
−
Do not install on the same panel as a high-voltage device.
−
Ensure a distance of at least 50mm from a duct or near-by module.
−
Ensure that it is grounded in a place free from noise.