1. Introduction
1.2. Terminology
R200
Isolated Analog Output Module 2MLF-DV4S, 2MLF-DC4S User's Guide
21
September 2010
Honeywell
Current output
The following figure illustrates the characteristic of the D/A conversion (current output).
When the current output range of the D/A conversion module is 4~20mA, the output is
4mA if the digital input is 0. The output is 20mA if the digital input is 16000, where
analog value converted from digital input of 1 is equivalent to 1
µ
A
.