F116 (SERIES 16000) SELF-CONTAINED DUCTABLE COMMERCIAL AIR CLEANER

68-0200

11

THREADED 
ROD

HEX BOLT

LOCK 
WASHER

TOP OF 
AIR CLEANER
CABINET

JAM
NUT

JAM NUT
3/8 x 16T

EYEBOLT

CHAIN

3/8 x 16T NUTS INSTALLED
IN CABINET CORNERS

FASTEN SECURELY TO STRUCTURAL SUPPORT SYSTEM
I.E. BAR JOIST, CONCRETE SLAB, TIMBER FRAMING, ETC.

ALL EXTERNAL HARDWARE
FURNISHED BY OWNER.

M10802

Fig. 13. Fastening air cleaner to a structural support

system (bar joist, concrete slab or timber framing).

Install with Ducting

Use a transition or box plenum to attach the ducting to air
cleaner inlet. A transition plenum is preferred. See Fig. 14. A
diffusion screen must be installed when a box plenum is used.
See Fig. 15. A box plenum can accommodate more than one
inlet.

M7793A

AIR CLEANER

Fig. 14. Transition plenum connected to the

air cleaner inlet.

DIFFUSION
SCREEN

M10803

AIR
CLEANER

Fig. 15. Box plenum with diffusion screen and three inlets

connected to the air cleaner.

M7792A

AIR CLEANER

SQUARE-TO-ROUND
CONNECTION

Y-BRANCH

Use a square-to-round or square-to-square connection when
attaching the air cleaner outlet to the blower discharge
flange. See Fig. 16. The outlet connection can be used with
a Y-branch, distribution box or manifold as required.

Fig. 16. Square-to-round connection attached to the air

cleaner outlet.

Wire

All wiring must comply with applicable codes and ordinances.
The power source must agree with the air cleaner electrical
rating (120 Vac, 60 Hz).

1. Connect the power. See Fig. 17 and 18.

IMPORTANT

Ground the air cleaner for proper operation and
safety.

2. Turn on the power and check that the blower operates

at all three speed settings.

3. Check that the ON indicator lights when the fan is

operating.

4. Turn off the power and install the filters in the cabinet.

NOTE:

Select models have a disposable aluminum
spacer. The spacer is necessary only when
using the CPZ™ modules. All other filters need
to remove and save the spacer for future
needs.

5. Replace the air cleaner cover.

Fig. 17. F116A1021, F116A1047 and F116A1120

series 16002, 16004 and 16012)  air cleaner typical

wiring diagram.

BLACK (HIGH)

BLUE (MEDIUM)

RED (LOW)

BROWN

BROWN

BLOWER 
MOTOR

GROUND

GROUND

LINE

120 VAC

OIL FILLED CAPACITOR —
CHECK NAMEPLATE FOR
CORRECT VALUE

WHITE (COMMON)

M10805

Summary of Contents for 16000 Series

Page 1: ...ansported by a network of ducting and plenums or the unit can be used independently FEATURES Variety of filter configurations available to customize the air cleaner for any application Three speed direct drive forward curve blower motor circulates up to 2500 cfm 72 m3 min for large areas Negative and positive pressure rooms can be created with the air cleaner Charcoal permanganate and zeolite CPZ ...

Page 2: ...net uses a prefilter with two primary filters Refer to Table 1 for model descriptions Construction 0508 in 16 GA unpainted aluminum Table 1 F116 Series 16000 Description a Primary filters must be ordered separately The choices include a 95 D O P filter ASHRAE dust spot filter or two sorbent modules b Second primary filter must be ordered separately The choices include a 95 D O P filter ASHRAE dust...

Page 3: ...r Volume Internal Static Pressure and Hanging Weight with Filters Model Numbers Filter Configuration Recommended Air Volume in cfm m3 min Approximate Internal Static Pressure at Recommended Air Volume Hanging Weight with Filters in lbs kg F116A1021 16002 HEPA filter 99 997 1600 49 1 3 W G 149 68 F116A1047 16004 D O P filter 95 1800 52 1 1 W G 130 59 ASHRAE dust spot filter 95 2000 58 1 0 W G 108 4...

Page 4: ... 24 x 24 x 12 610 x 610 x 305 95 ASHRAE dust spot at 2000 cfm 58 m 3 min In metal frame 24 x 24 x 12 610 x 610 x 305 65 ASHRAE dust spot at 2000 cfm 58 m 3 min In metal frame Sorbent Module Contents charcoal only permanganate only zeolite only or CPZ material combination of the above ingredients 111 2x 111 2 x 23 292 x 292 x 584 85 first pass at 1600 cfm 49 m 3 min for most gases odors Ten panel d...

Page 5: ... 4 565 16 TYP 406 5 TYP 127 3 8 THREADED INSERT HOLE FOR HANGING INSTALLATION HEPA D O P OR ASHRAE FILTER ELECTROSTATIC PRECIPITATOR COLLECTING CELLS PREFILTER SORBENT MODULES M10810 TOP 7 8 22 FLANGE 12 1 8 308 13 1 2 343 10 254 7 178 FRONT VIEW Fig 1 Approximate dimensions of two stage filtering model in in mm ...

Page 6: ...TOR COLLECTING CELLS PLANNING THE INSTALLATION WARNING Explosion Hazard Possible Can cause personal injury or equipment damage Do not install or use where there is any danger of gas vapor or dust explosion Do not install when explosion proof electrical fixtures are specified Application and Operation The F116 series 16000 self contained ductable commercial air cleaner is designed for use in smokin...

Page 7: ...s approximately 2350 cfm 68 m3 min and at 1 7 W G the air volume is approximately 2000 cfm 58 m3 min But at 1 9 W G the air volume drops to approximately 1150 cfm 33 m3 min Loading does not resist airflow when using the electrostatic precipitator collecting cells and or CPZ modules However a loaded prefilter does restrict the airflow Refer to Fig 3 and Table 3 for nominal air volume calculations a...

Page 8: ...ositioning air cleaners at the far end of the restaurant smoking section to draw the smoke away from the nonsmoking section Fig 5 Positioning air cleaners to create a negative pressure in polluted spaces and creating a positive pressure in nonpolluted areas Use this positioning in in plant offices and hospitals M7782 ...

Page 9: ...air cleaner to create a negative pressure booth that contains a contamination generating process Fig 8 Positioning air cleaner to remove pollutants from a conveyor feed process such as screen printing TOP VIEW CURTAIN CONVEYOR DRYER HOOD INPUT CURTAIN OUTPUT DRYER INPUT SIDEVIEW M10797 AIR CLEANER AIR CLEANER Fig 9 Positioning air cleaner to create positive pressure for a plant satellite office PO...

Page 10: ...HERE IS HEAVY OIL SMOKE COOKING HEAVY WELDING OR HEAVY CUTTING M10800 AIR CLEANER DO NOT INSTALL WHERE THERE IS HEAVY OIL SMOKE COOKING HEAVY WELDING OR HEAVY CUTTING M10801 AIR CLEANER Fig 11 Connecting air cleaner directly to a canopy hood with a minimum air entrance velocity of 120 fpm Fig 12 Positioning air cleaner to recirculate existing exhaust system air which contains light to medium quant...

Page 11: ...nd or square to square connection when attaching the air cleaner outlet to the blower discharge flange See Fig 16 The outlet connection can be used with a Y branch distribution box or manifold as required Fig 16 Square to round connection attached to the air cleaner outlet Wire All wiring must comply with applicable codes and ordinances The power source must agree with the air cleaner electrical r...

Page 12: ...ity and type of contaminants present and the frequency of air cleaner use The cell performance indicator is on when the primary filters need to be replaced or cleaned The frequency of servicing can only be established after a period of use NOTE Some full service distributors provide regular servicing to commercial establishments CAUTION Turn off power to the air cleaner Stand on a stable platform ...

Page 13: ...or optimum water drainage from tubes stand the cell on one of its corners 6 Wipe ionizer wires to remove any deposits remaining on the wires 7 Check the collection plates of the cells for any detergent residue Repeat the rinse process if there is any residue remaining Buildup can reduce the air cleaner efficiency About Discolored Aluminum Occasionally the cells can seem stained after the soaking p...

Page 14: ...end warped or bent collector plates back into shape For maximum efficiency replace broken ionizer wires as instructed in Replacing Ionizer Wires section 2 Wipe ionizer wires 3 Check that cells are completely dry before reinstalling in the air cleaner If cells are placed into the air cleaner while still wet the electronic cells can short out and arc frequently when almost dry Although the system ap...

Page 15: ...ors or ducting plug air leaks ELECTROSTATIC PRECIPITATOR COLLECTOR CELL MODELS ONLY No high voltage to cells Check wiring for loose connections tighten Check for short in cells or configuration wires fix Check door interlock switch fix Check power supply pressure switch fix Check contact boards for ground ground Check for wet cells and ionizer wires allow time for the cells and wires to dry Replac...

Page 16: ...imary Filters HEPA filter 99 97 1 32000198 860023 D O P filter 95 1 32000195 860024 ASHRAE dust spot filter 95 1 32000196 860025 ASHRAE dust spot filter 65 1 32000197 860026 CPZ sorbent module requires 2 1 32000219 31005 Charcoal only sorbent module requires 2 1 32000220 31006 Zeolite only sorbent module requires 2 1 32000221 31007 Permanganate only sorbent module requires 2 1 32000222 31008 Elect...

Page 17: ...17 ELECTROSTATIC PRECIPITATOR COLLECTING CELL 1 PREFILTER 2 SORBENT MODULES M10812 HEPA D O P OR ASHRAE FILTERS 1 1 TWO STAGE MODELS WILL HAVE ONLY ONE PRIMARY FILTER AREA 2 2 Fig 23 Exploded view of F116 series 16000 self contained ductable commercial air cleaner components ...

Page 18: ...RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PRODUCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND HONEYWELL INC EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES WHETHER WRITTEN OR ORAL IMPLIED OR STATUTORY I...

Page 19: ...F116 SERIES 16000 SELF CONTAINED DUCTABLE COMMERCIAL AIR CLEANER 68 0200 19 ...

Page 20: ...ng Kong Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 68 0200 J H 1 98 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post consumer paper fi...

Reviews: