Electrical Ratings:
Running Load (all three fan speeds): must not exceed
14A at 120V.
Refer to Table 2 for maximum starting loads.
Table 2. F116 (Series 16000) Maximum Starting Loads.
(continued)
Fan Setting
Voltage
Amperes
High
120V
23A
Medium
120V
15A
Low
120V
15A
Air Volume, Internal Static Pressure and
Installation Weight:
Air volume, internal static pressure and installation weight are
based on the air cleaner filter configuration. Refer to Table 3.
Filtration Efficiency:
See Table 4.
Power:
Hardwire
Approvals:
UL and cUL pedning.
Dimensions:
See Fig. 1 and 2 for dimensions.
Replacement Parts and Accessories:
See Parts List on page 16.
Table 3. F116 (Series 16000) Filter Configuration, Recommended Air Volume,
Internal Static Pressure and Hanging Weight with Filters.
Model Numbers
Filter Configuration
Recommended Air
Volume in cfm
(m
3
/min)
Approximate Internal
Static Pressure at
Recommended Air
Volume
Hanging Weight
with Filters in
lbs (kg)
F116A1021 (16002)
HEPA filter (99.997%)
1600 (49)
1.3" W.G.
149 (68)
F116A1047 (16004)
D.O.P. filter (95%)
1800 (52)
1.1" W.G.
130 (59)
ASHRAE dust spot filter
(95%)
2000 (58)
1.0" W.G.
108 (49)
ASHRAE dust spot filter
(65%)
2000 (58)
0.75" W.G.
108 (49)
CPZ™ sorbent modules
1600 (49)
0.5" W.G.
143 (65)
F116A1120 (16012)
D.O.P. filter and CPZ™
sorbent modules
1600 (49)
1.3" W.G.
198 (90)
ASHRAE dust spot filter
(95%) with CPZ™ sorbent
modules
1600 (49)
1.0" W.G.
175 (79)
ASHRAE dust spot filter
(65%) with CPZ™ sorbent
modules
1600 (49)
0.8" W.G.
175 (79)
Two sets of CPZ™ sorbent
modules
1600 (49)
0.8" W.G.
211 (96)
ASHRAE dust spot filter
(65%) with D.O.P. filter
1800 (52)
1.5" W.G.
162 (74)
Two ASHRAE dust spot
filters (65%)
2000 (58)
1.6" W.G.
139 (63)
ASHRAE dust spot filter
(95%) with D.O.P. filter
Not recommended