Zone/Sounder Indications
Repeat Panel Fault Indications
System Fault (Software) Indications
Fault finding
Fire Panels
19
4188-424 issue 4_Part 1_10-09
Visual Indications
Audible
Indications
Signals out
Condition
Zone
Fault
(1-8) -
Yellow
Fault -
Yellow
Sounder
- Yellow
Disabled
- Yellow
Power -
Green
Buzzer
Aux Relay
contacts
Normally
de-
energised
Common fault
-
Normally active
Common
fire-
Normally
deactive
Zone
fault
Pulse
slowly
Steady
On
Pulse slowly
Normal
Deactive
Deactive
Sounder
fault
Steady
Pulse
slowly
On
Pulse slowly
Normal
Deactive
Deactive
Disable
zone
On
On
On
Normal
Active
Deactive
Disable
Sounder
On
On
On
Normal
Active
Deactive
Visual indications
Audible
indication
Signals out
Condition
Fault -
Yellow
Power -
Green
Access/
Function -
Yellow
Buzzer
Aux Relay contacts
Normally de-energised
Common fault
-
Normally active
Common fire-
Normally deactive
Repeat
Panel Link
Fault
Steady
On
Pulse
slowly
Pulse
slowly
Normal
Deactive
Deactive
Visual indications
Audible
indication
Signals out
Condition
Fault -
Yellow
System -
Yellow
Power -
Green
Buzzer
Aux Relay contacts
Normally de-energised
Common fault
-
Normally active
Common fire-
Normally deactive
Software
system
fault
On
On
On (Pulses
at Repeat
panel)
On
Normal
Deactive
Deactive