Access levels 2
To configure the system enter the
appropriate access code.
NOTE:
It is only necessary to
enter the access code once,
provided the 2 minute timeout is
not exceeded between button
presses.
Access codes
Factory set codes are:
Access level 2 Code : 123
Depending on how the system is
configured coded entry may be
necessary for test.
The factory codes can be
changed at any time after power
up.
NOTE:
It is important to leave
the system in a normal
operating condition on
completion of commissioning.
NOTE:
The auxiliary contacts do
not operate in the Test Modes.
Fire Panels
Access levels 2
4188-424 issue 4_Part 1_10-09
12
Operating Instructions for AL2 functions
How to do a Display test
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
display
buttons and check that all indicators are lit.
How to set the panel to operate in Test mode A
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
3
buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested without an alarm of fire
How to set the panel to operate in Test mode B
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
4
buttons followed by the number of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested with 2 seconds alarm of fire.
How to cancel Test mode A/B
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
5
buttons followed by the number of the zone to have test mode cleared.
- The test mode A or B is cancelled.
How to disable a zone
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
1
buttons followed by the number of the zone to be disabled.
- Check that the appropriate Zone fault indicator and the Disabled indicator are lit.
- A detected fire in the disabled zone will not cause the panel to go into fire condition.
How to enable a zone
q
Enter the AL2 access code and check that the Access/function lamp is lit.
q
Press the
shift
and
2
buttons followed by the number of the zone to be re-enabled.
- The previously disabled zone is re-enabled.