8.
Application as per VdS
9.
Technical data
- The power supply may not be connected parallel.
- The temperature sensor for the power supply must be fixed to the battery.
- The power supply must be installed in a metal housing.
- The battery must be fixed with Velcro (
.
Dual lock fasteners)
Rated operating voltage
230 V AC
Operating voltage range
-15 % to +10 %
Frequency
40 Hz to 60 Hz
Power consumption
100 VA
Maximum constant current
1.5 A
Short-term continuous current drain (5 min.)
2.2 A max.
Maximum charging current
1.5 A
Approved accum. capacity as per VdS
40 Ah max.
No. of connectible accumulators
2 max.
Possible accumulator combinations
e.g. 2x10 / 2x16 / 1x24 / 1x38 Ah
Current consumption as per VdS for 60 hours:
at 40Ah accumulator capacity
Approx. 650 mA
Permanent accumulator monitoring
Temperature-guided accum. charging voltage
Operating temperature range
-5 °C to +45 °C
Storage temperature range
-25 °C to +70 °C
Environmental Class as per VdS
II
PCB dimensions:
97.5 x 250 mm
(
)
with charged accum.
8 Mounting and Connection Instructions Mains/charger unit 12 V DC / 40 Ah
P00212-10-002-05
2013-09-16
© 2013 Novar GmbH
Honeywell Security Group
Novar GmbH
Johannes-Mauthe-Straße 14
D-72458 Albstadt
www.honeywell.com/security/de