1.
General
Fully electronic mains/charger unit.
- Voltage-stabilized, current limited
- Redundancy standby operation
- Deep-discharging protection
- Charging circuit monitoring
- Recognition of defective batteries
- Accumulator capacity up to max. 40 Ah
When selecting the size of housing, pay attention to the
space required for the accumulators.
2.
VdS guidelines for power supply
The power supply must be connected to the mains with a
separate fuse.
If the electrical installation has an earth-leakage circuit breaker
(Fl switch), the energy supply must have its own earth-leakage
circuit breaker. The fuse and Fl switch should, if possible, be
within the security zone.
If the energy supply is not part of the control panel, it must be
installed in the immediate vicinity (without a space between) so
that an attack on the connection line is impossible without
causing mechanical damage to the housing.
The control panel and power supply should, if possible, be
screwed together.
Users not belonging to the system should not be connected to
the mains voltage.
The accumulators used in the power supply must be
approved. For parallel switching, only accumulators of the
same age and from the same production series are allowed
to be used.
The accumulators must be fixed on the housing base using
Dual lock fasteners
(Item no. 055280).
3.
Mounting
Attention
Safety instructions
When performing installation work of any kind, the unit must
be de-energized.
When installing the power unit in a control panel housing or
equivalent, ensure that the supplied
insulating foil has been
inserted between the housing base and the underside of
the PCB.
Note, that the power unit is screwed tight to the
housing base.
The non-fused earth conductor from the electric power circuit
must be connected in the immediate vicinity of the connection
terminals of the supply voltage.
The power supply line must be fixed when connecting so that
the
clearance (4 mm)
and
creep paths (5 mm)
between the
electronic modules and/or their periphery and the power
supply line are not shorter than stipulated.
If the neutral line cannot be clearly identified, a second pro-
tection must be available in the electric power circuit so that
2-pole separation from the electric circuit is possible.
The connection terminals must be protected against touching
inadvertantly by using the supplied cover.
4.
Functional description
Two independent control circuits are installed on the mother-
board.
- First control circuit:
Supplies the control panel and the external users.
- Output
control panel supply
with 2.5 AF fuse (including ext. user)
- Output
external user
with 2x1 AF fuse (2 outputs together).
- Second control circuit:
Serves as a charger for the accumulators. The charging
current is limited to 1.5 A.
The accumulator charging voltage is monitored and ad-
justed according to the temperature with the aid of an NTC
resistor.
The
charge terminating voltage
has been correctly set
before leaving the factory (for
Sonnenschein A500 series
).
If it requires resetting, proceed according to Chapter 5 "Set
charge terminating voltage".
The supply voltage for the control panel and external users do-
es not require adjusting as it is monitored and adjusted by the
accumulated charging voltage so that in case of a mains failure,
large voltage jumps are avoided.
Voltage surge protection:
The power supply is equipped with a voltage surge protection
which is triggered should the output voltage
exceed 17 V DC
in case of a fault.
Mounting and Connection Instructions
Mains/charger unit 12 V DC / 40 Ah
Item no. 010690.02
G197099 IDS
Seite 1 - 4 Page 5 -8
D
GB
P00212-10-002-05
Subject to change
without notice
2013-09-16