background image

 

LED INDICATORS 

The SiXCOMBO has a multi-color top LED:  

Green =   Supervisory indication; blinks during power on, 

 

reset, and during normal operation 

Amber =   Signal maintenance and trouble events 

Red =   Alarm condition (either Smoke, CO, or Heat) 

Side LED windows indicate alarms:  

Red =   Smoke 

Blue =   CO 

 

CLEANING 

IMPORTANT:

 This detector must be tested and maintained 

regularly following NFPA-72 requirements.  The detector should 

be cleaned at least once a year.

 

1.  Remove the detector from the base plate by turning 

counterclockwise. 

2.  Clean the outside casing with a cloth. Ensure that the holes 

on the front of the alarm are not blocked with dirt and dust. 

Canned air can be used to remove any dust or debris. 

3.  Reattach the detector to the base plate by rotating 

clockwise.  

4.  Test the detector to insure it is fully functional. (See Testing 

section). 

5.  Notify the proper authorities and Central Station when the 

system is back in service 

REPLACING THE BATTERIES 

 

 

CAUTION:  

The batteries used in this device may present a fire 

or chemical burn hazard if mistreated.  Do not recharge, 

disassemble, heat above 100°C (212°F) or dispose of in fire.  

Use only Panasonic CR123A Lithium batteries. Use of other 

batteries may present a risk of fire or explosion. Keep used 

batteries away from children.  Dispose of used batteries 

properly. 

 

Remove old batteries.  Wait 10 seconds and then replace with 

four new batteries. To avoid a low battery indication when 

installing new batteries, all 4 batteries must be installed within 

15 seconds of installing the first one. Any low battery condition 

that may have occurred should clear when the base plate is 

installed.  

 

NOTE:

 Constant exposure to high or low temperature or high 

humidity may reduce battery life. 

 

LIMITED LIFE OF CO SENSOR

 

This detector is manufactured with a long-life electrochemical 

carbon monoxide sensor. Over time the sensor will lose 

sensitivity and will need to be replaced. The life span of the CO 

sensor is approximately ten years from the date of manufacture. 

Periodically check the detector’s replacement date. Remove the 

detector head and refer to the ‘replace by’ sticker placed on the 

underneath side of the detector. The sticker will indicate the 

date the detector should be replaced. 

Reminder:

 This detector is also equipped with a feature that will 

signal the panel once the CO sensor has passed the end of its’ 

useful life. If this occurs, it is time to replace the detector. 

What to do if the detector goes into CO alarm: 

If the detector goes into CO alarm (4 beeps), immediately 

move to a spot where fresh air is available, preferably 

outdoors, where the air is safe and call your security service 

provider.  Tell your provider the detector alarm status, and that 

you require professional assistance in ridding your home of the 

carbon monoxide.   

This detector is NOT: 

  A substitute for the proper servicing of fuel-burning 

appliances or the sweeping of chimneys. 

  To be used on an intermittent basis or as a portable alarm 

for the spillage of combustion products from fuel-burning 

appliances or chimneys. 

Carbon monoxide gas is a highly poisonous gas which is 

released when fuels are burnt. It is invisible, has no smell and 

is therefore is impossible to detect with the human senses. 

Under normal conditions in a room where fuel burning 

appliances are well maintained and correctly ventilated, the  
amount of carbon monoxide released into the room by 

appliances should not be dangerous. 

 

CAUTIONS

:  

  This device will only indicate the presence of carbon 

monoxide gas at the sensor. Carbon monoxide gas may be 

present in other areas. 

  This device is designed to protect individuals from the acute 

effects of carbon monoxide exposure. It will not fully 

safeguard individuals with specific medical conditions. If in 

doubt consult a medical practitioner. 

  Installation of the device should not be used as a substitute 

for proper installation, use, and maintenance of fuel-burning 

appliances, including appropriate ventilation and exhaust 

systems.

 

MAINTENANCE 

Do not paint, and do not use cleaning agents, bleach or 

polish the detector. 

NOTE:

 Before performing any maintenance on the 

detector, notify the proper authorities and Central Station 

that maintenance is being performed and the system will 

be temporarily out of service. Disable the zone or system 

undergoing maintenance to prevent any unwanted alarms. 

Power must be removed from the detector before 

performing maintenance of any kind. 

 

The SiXCOMBO detector reports maintenance issues to the 

control panel and communicates them visually and audibly per 

Table 2. 

Trouble feature:

 When the sensor (supervision) is in a trouble 

condition (such as a detector that is dirty or CO sensor non-

functioning), the detector will send a trouble signal to the 

control panel. Depending on the issue, the detector must then 

be serviced or replaced. 

NOTE:

 Smoke detectors are not to be used with detector 

guards unless the combination is evaluated and found suitable 

for that purpose.

 

SYMPTOMS OF CARBON MONOXIDE POISONING 

Carbon monoxide bonds to the hemoglobin in the blood and 

reduces the amount of oxygen being circulated in the body. 

The following symptoms are examples taken from NFPA 720; 

they represent approximate values for healthy adults. 

 

Concentration 

(ppm CO) 

Symptoms 

200 

Mild Headache after 2-3 hours of exposure 

400 

Headache and nausea after 1-2 hours of exposure 

800 

Headache, nausea, and dizziness after 45 minutes 

of expo- sure; collapse and unconsciousness after 2 

hours of exposure 

Many cases of reported carbon monoxide poisoning indicate 

that while victims are aware that they do not feel well, they 

become so disoriented that they are unable to save 

themselves by either exiting the building or calling for 

assistance. Also, young children, elderly and pets may be the 

first to be affected. 

CO ALARM ACTIVATION 

Per UL standard 2075, the SiXCOMBO detector has been 

tested to the sensitivity limits defined in UL standard 2034. 

CO Alarm Thresholds 

Parts per Million (ppm) 

Detector Response Time (Min.) 

30+-3ppm 

No alarm within 30 days 

70+-5ppm 

60-240 

150+-5ppm 

10-50 

400+-10ppm 

4-15 

 

SPECIFICATIONS   

Electrical Specifications 

Voltage: ...................................................................... 3 volts DC 

Battery Type: ..................................................... CR123A lithium 

Battery Manufacturer: .......................... Panasonic CR123A only 

Number of Batteries: ................................................................ 4 

Sensitivity: .... UL limits .9 to 3.50%/ft / ULC limits .9 to 3.08 %/ft  

Thermal alarm: .................................................... 135° F (57° C) 

Audible Signal: ................................................................ 85dBA 

Physical Specifications 

Diameter: ................................. 6.3 in. Diameter x 1.65 in. Thick  

 

(16.002 cm x 4.19 cm Thick) 

Weight: ............................................................... 14.3 oz (406 g) 

Operating Temperature Range: ........... 32° - 100° F (0° - 38° C) 

Storage Temperature Range: .............. 14 - 158° F (-10 - 70° C) 

Operating Humidity Range: ...................................... 20-95% RH

Summary of Contents for SiXCOMBO

Page 1: ...rollment process 4 The device attempts enrollment green LED flashes about 8 seconds If successful the green LED lights steady for 3 seconds and the device announces successful enrollment If the LED does not light steady enrollment failed Retry by pressing either Test switch for less than 3 seconds All services Smoke Heat and CO are automatically enrolled in sequential or next available zone number...

Page 2: ...ing a Smoke alarm if an alarm condition still exists after the 5 minute hush period the alarm will sound The hush feature will not operate at levels above 4 ft smoke concentration During a CO alarm if carbon monoxide is still present after the 5 minute hush period the alarm will sound The hush feature will not operate at levels above 350 ppm parts per million carbon monoxide CO SENSOR END OF LIFE ...

Page 3: ...possible to detect with the human senses Under normal conditions in a room where fuel burning appliances are well maintained and correctly ventilated the amount of carbon monoxide released into the room by appliances should not be dangerous CAUTIONS This device will only indicate the presence of carbon monoxide gas at the sensor Carbon monoxide gas may be present in other areas This device is desi...

Page 4: ...rme NMB 003 du Canada FCC IC STATEMENT This device complies with Part 15 of the FCC Rules and Industry Canada s license exempt RSSs Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation Cet appareil est conforme à la partie 15 des règles ...

Reviews: