Error messages
Error display
Error description
Measures/notes
• Hardware error or
damaged
fi
rmware
• Supply flow sensor
broken
• Supply flow sensor
short-circuit
• Return flow sensor
broken
• Return flow sensor
short-circuit
• Check flow sensor, connection
cable and calculator unit for external
damage
• Device must be replaced
• Check temperature sensor and pipes
for mechanical damage
• Device must be replaced
• Check temperature sensor and pipes
for mechanical damage
• Device must be replaced
• Check temperature sensor and pipes
for mechanical damage
• Device must be replaced
• Check temperature sensor and pipes
for mechanical damage
• Device must be replaced
Error messages with module in place
Error display
Error description
Measures/notes
• Add-on module has
been paired with
another metering
device before
• The module has the
measuring data of
another meter
• Low power
(radio add-on module)
• Radio add-on module
not initialised (clock
wrong)
• Save data, since these are overwrit-
ten after a short time
• Press any key to delete the display
• After deletion the new add-on mod-
ule will be accepted
• Maximum operating duration expired
• Add-on module must be replaced
• Add-on module must be replaced
Fault messages with the ultrasonic measurement system
Error display
Error description
Measures/notes
• Air in the measure-
ment section
• No correct ultrasonic
measurement signal
• Vent pipework
Summary of Contents for resideo EW701
Page 2: ...2 MU2H 0501ge23 R1020 V1 00 3 5 2018 2020 Resideo Techonologies...
Page 4: ...V1 00 3 5 2018 MU2H 0501ge23 R1020 3...
Page 218: ...216 MU2H 0501ge23 R1020 V1 00 3 5 2018 Dimensions EWA600C MBUS 78 48 10 8 28 4 34 1...
Page 219: ...V1 00 3 5 2018 MU2H 0501ge23 R1020 217 Dimensions EWA600C RF 78 48 11 29...
Page 222: ...220 MU2H 0501ge23 R1020 V1 00 3 5 2018 FUM5HWHEDES EW701...