EN
44
MU2H-0501ge23 R1020
V1.00 / 3.5.2018
Installing temperature sensors
Installation set temperature sensor directly immersed
There is an installation set included for meters with 5.2 × 45 mm temperature
sensors. This can be used to
fi
t the sensor directly immersed in the ball valve.
Carry out steps 1–4 with the position P1 shown for the
1
P1
P2
temperature sensor (TF) in the half-shell
2
screw fitting.
(1) Insert the temperature sensor in the
half-
shell screw fitting enclosed.
(2)
Fit the second half of the screw fitting
in such a way that the locking pin of the
one half fits into the recesses of the other
half.
Immersion
depth > 50 %,
< 99 %
3
(3) Position the O-ring at the instal-
lation point in the ball valve.
Use the genuine O-ring from the
kit enclosed!
(4) Push in the TF and use a tightening
torque of approx. 3 Nm (hand-tight) to
tighten the screw fitting.
The temperature sensor
4
must not touch the base
of the ball valve.
Check for correct TF installation:
(a) Collars of the half-
shell screw fitting are
flush to the ball valve
(b)
Shells of the screw fitting are flush
to
one another
If TF installation has not been successful,
the TF must be removed from the ball valve
again.
Then carry out steps 1-4 with the position
sensor (TF) in the half-
shell screw fitting.
shown for the temperature
P2
right
wrong
a
b
Summary of Contents for resideo EW701
Page 2: ...2 MU2H 0501ge23 R1020 V1 00 3 5 2018 2020 Resideo Techonologies...
Page 4: ...V1 00 3 5 2018 MU2H 0501ge23 R1020 3...
Page 218: ...216 MU2H 0501ge23 R1020 V1 00 3 5 2018 Dimensions EWA600C MBUS 78 48 10 8 28 4 34 1...
Page 219: ...V1 00 3 5 2018 MU2H 0501ge23 R1020 217 Dimensions EWA600C RF 78 48 11 29...
Page 222: ...220 MU2H 0501ge23 R1020 V1 00 3 5 2018 FUM5HWHEDES EW701...