EU-90
Date Revised: March 2021 (PSV52522-S)
© 1998-2021 American Honda Motor Co., Inc.—All Rights Reserved
EU M
o
dels
AC OUTPUT
Use a load bank (available through the Honda Tool and Equipment Program or the Parts Division) to verify the customer’s
initial complaint and the generator’s performance after the repairs (see
).
COMPLAINT: Abnormal output (none, low, or high) at receptacle.
Normal:
120 VAC ± 10.
The circuit protectors must be in the ON position.
WARNING
High voltage and electrical current present. Touching the non-insulated portions
of the meter leads or generator wiring can cause shock or electrocution.
Wear insulated gloves and avoid handling non-insulated wiring.
1.
Does the engine start and run, or stop
shortly after it is started?
STOPS
.
2.
Start the engine
and verify that
the output
indicator is ON.
ON
• Check the receptacles.
• Check the circuit
protectors.
• Check the voltage
selector switch.
• Check the wiring from
the inverter to the control
panel.
3.
With a fully charged battery installed, turn the engine switch to the ON position.
4.
Push and hold the i-Monitor button for 3 seconds. If an error
code (E-XX) is displayed, record the code. Push the
i-Monitor button again and record additional codes until END
appears.
CODE(S)
Troubleshoot the most recent error
code(s) according to the itemized
list starting on
Use the
EU7000is
i-Monitor Detail
Error Log
located in the TEST
WORKSHEETS chapter of this
manual to record error codes and
the detail error log information for
each error code.
5.
Start the engine and verify the engine speed.
Specified engine speed:
Eco Throttle
®
OFF: 3,300
±
100 rpm
Eco Throttle ON: 2,400
±
100 rpm
NG
Refer to
Hard Starting
in the shop
manual Troubleshooting Section.
on the next page.
RUNS
OUTPUT
INDICATOR
OFF
OK
I-MONITOR
BUTTON
ERROR CODE
DISPLAY
NO CODE
OK