(Inverter unit overheated protection activated)
1. Disconnect the AC appliance and stop the engine.
2. Reset the error log
and turn the main switch OFF.
3. Check the front cover cooling air passage for blockages. Remove any blockages.
4. Wait for several minutes.
With the engine running at normal operating temperature, check to see if an error code is displayed in the error log mode
. If the same error code occurs, replace the inverter unit and recheck.
,
(Inverter unit internal failure: A/D input error)
1. Perform the engine start procedure twice.
2. Check to see if an error code is displayed.
If the same error code occurs, replace the inverter unit and recheck.
, , , , , , , ,
(Inverter unit internal failure: FET open/FET short/Diode line short/SCR short)
,
(Inverter unit internal failure: RAM/ROM failure)
1. Perform the engine start procedure.
2. Check to see if an error code is displayed.
If the same error code occurs, replace the inverter
unit
.
3. Perform the engine start procedure.
Check the stator
.
Call Techline before replacing the
stator.
Abnormal
Normal
Replace or repair the wire harness.
Abnormal
Normal
Restart the engine twice and check to see if an error code is displayed. If the
same error code occurs, replace the inverter unit and recheck. Call Techline
before replacing the inverter.
Check the control panel main wire harness for an open or short circuit.
Check the inverter unit inspection.
Call Techline before replacing the
inverter unit.
Abnormal
Normal