Homeworks HQWT-T-HW Installation Instructions Manual Download Page 2

2.  Select the system type. 

Use the 

Basic Configuration Parameter Table

 to set up 

the system type. The display will show the first parameter ID “01b” and go through 

all applicable parameter IDs.

Note:

 Not all parameter values will be available for every parameter ID. Only the 

parameter values that apply to the selected system type will be shown.

3.  Select the desired parameter value. 

Press 

Set

 or 

Set

 to indicate the desired 

parameter value. Press 

Set

 to proceed to the next applicable parameter ID. 

Repeat until all desired parameter values have been selected.

4.  Save parameter values and exit basic configuration mode. 

When “End” is shown, press and hold 

Set

 until the backlight 

flashes and the display shows the current room temperature 

(3 seconds).

Reenter Configuration (optional)

If any changes are needed after configuration has been completed, follow the steps 

below.

1.  Press and hold 

Set

 and 

Set

 until the backlight flashes (3 seconds).

2a.  

For controller selection mode -

 Release the buttons and immediately press and 

hold 

Set

 until the backlight stops flashing and "CO" is shown (3 seconds).

2b.  

For basic configuration mode -

 Release the buttons and immediately press and 

hold 

Set

 until the backlight stops flashing and “bA” is shown (3 seconds).

To learn about how to configure advanced system settings or 

to verify proper system functionality, see the HomeWorks QS 

Palladiom Thermostat Configuration Guide (P/N 032498) at  

www.lutron.com

WARNING:  Shock / Fire  Hazard.

 Improper configuration or installation can 

cause property damage, personal injury, or death. Installation and service 

must be performed by a licensed professional HVAC installer (or equivalent) or 

service agency.

Note:

 Configuration is required when a new thermostat is added.

HVAC Controller Selection Mode

(only available with thermostat version 1.10 or later)

1.  Enter HVAC controller selection mode. 

When a thermostat receives power, it will 

automatically enter HVAC controller selection mode if an HVAC controller has not 

been previously selected.

If no HVAC controller is going to be connected directly to the thermostat, skip this 

section. This configuration will be completed by a certified Lutron dealer via the 

HomeWorks QS Designer software.

2.  Select value for parameter ID "01": Select the HVAC controller connected to 

the thermostat. 

Using the table below, press 

Set

 or 

Set

 to select the correct HVAC 

controller being used and press 

Set

.

Values based on HVAC controller

SMC55-RESI

Mitsubishi 

A1M

Cool Automation 

CoolPlug

LG 

PDRYCB500

Parameter ID 01: 

HVAC controller 

option

01

02

03

04

Parameter ID 02: 

Modbus address

01

00-30  

(set by DIP 

switches 

1-5)*

99

01-08  

(set by DIP 

switches 1-4)*

3.  Select value for parameter ID "02": Set the Modbus address.* 

Using the table 

above, press 

Set

 or 

Set

 to select the desired Modbus address and press 

Set

.

*  For more information, see the instructions included with the HVAC controller.

4.  Exit HVAC controller selection mode. 

When “End” is shown, 

press and hold 

Set

 until the backlight flashes (3 seconds). 

If SMC55-RESI was selected, proceed to the next section. 

Otherwise, skip the next section.

Note:

 "E1" will show on the display if the thermostat is not able to communicate with 

the HVAC controller.

Note:

 If a new HVAC controller type or address is used, the HVAC controller 

selection mode will need to be reentered. See 

Reenter Configuration

 section.

Configuring the SMC55-RESI

1.  Enter basic configuration mode. 

If the SMC55-RESI was the HVAC controller 

selected in HVAC controller selection mode and it was not previously configured, 

basic configuration mode will automatically be entered.

Set

Parameter ID

Press to change 

parameter value

Press to select current 

parameter value and go to 

next parameter ID

Press to go back to previous 

parameter ID

Parameter value

bA =  Basic configuration 

mode

Lutron Electronics Co., Inc. 

7200 Suter Road, Coopersburg, PA 18036-1299 U.S.A.

®

Troubleshooting

Symptom

Possible Cause

Solution

Display is blank

The thermostat does not have power.

Check the wiring to confirm that Common (Black) and V+ (Red) are connected to 

a 24–36 V

-

 power supply.

E0 shown on the master thermostat

The thermostat temperature sensor is not functioning properly.

Contact Customer Assistance.

E0 shown on the companion 

thermostat

A companion thermostat will show E0 if the temperature sensor for that 

zone is missing.

Check the error code on the master thermostat.

E1 shown on the master thermostat

Wiring issue between the thermostat and the HVAC controller or HVAC 

controller does not have power.

Ensure that the HVAC controller communication link is wired correctly and 

isolated from all other connections and that the HVAC controller has power. 

The incorrect HVAC controller or modbus address was selected.

Enter HVAC controller selection mode and select the correct HVAC controller 

and modbus address.

E1 shown on the companion 

thermostat

Wiring issue between the processor and HVAC controller (if HVAC 

controller is connected to the processor). 

Check the wiring between the processor and HVAC controller.

The master thermostat (connected to the HVAC controller) is 

disconnected from the processor.

Ensure that the QS link between the master thermostat and the processor is 

wired correctly. 

E2 shown on the display

Remote temperature sensor is malfunctioning or misconfigured.

Check the wiring between the sensor and the HVAC controller and confirm 

configuration.

E3 shown on the display

Changeover sensor malfunctioning or misconfigured (applicable only for 

2-pipe systems).

Check the wiring between the sensor and the HVAC controller and confirm 

configuration.

E4 shown on the display

QS link wiring issue.

Contact Customer Assistance.

E5 shown on the display

Incorrect HVAC controller or thermostat model.

Ensure that SMC55-RESI and HQWT-T-HW are being used.

E6 shown on the display

Slab temperature sensor for underfloor heating is missing, malfunctioning 

or misconfigured.

Check the wiring between the slab sensor and the HVAC controller and confirm 

configuration.

System is not heating / cooling

The HVAC controller or HVAC equipment may not have power.

Ensure that the HVAC controller and HVAC equipment have power and are 

correctly wired. Consult an HVAC professional if the issue persists.

System is not heating / cooling as 

expected

Mounting location of the thermostat or remote temperature sensor is 

incorrect.

Refer to 

Mounting

 section.

Wiring issue between the HVAC controller and the HVAC system.

Check the wiring.

The HVAC system may not have power.

Ensure that the HVAC system has power.

Basic Configuration Parameter Table (for SMC55-RESI)

Parameter IDs

P

ar

am

et

er

 V

al

ue

s

01b:  System type

02b:  Heat stages

03b:  Run auxiliary heat 

(AUX / W

2

) with 

other heat stages

04b:  Auxiliary heat 

(AUX / W

2

) upstage 

delay

05b:  Cool stages

06b:  Heat fan control

07b:   Changeover / 

reversing valve 

(O/B)

08b:   Valve / 

Element 

Type

09b:  Fan Type

10b:  2-pipe mode

11b:  Under floor control

00 =  Conventional 

system

00 =  None

01 =  1 stage (W1)

02 =  1 primary source and 

1 auxiliary source (W2)

00 =  No

01 =  Yes

Skipped if no AUX / W

2

00 =  0 minutes

01 =  1 minute

02 =  2 minutes

03 =  5 minutes

04 =  10 minutes

05 =  20 minutes

06 =  30 minutes

07 =  1 hour

08 =  2 hours

09 =  4 hours

10 =  8 hours

11 – 24  =   11 – 24  hours
Skipped if no AUX / W

2

00 =  None

01 =  1 stage (Y1)

02 =  2 stages (Y1, 

Y2)

00:   Equipment 

controlled

01:   Thermostat 

controlled

N/A

N/A (relay)

N/A (single fan relay)

N/A

N/A

01 =  Heat pump

00 =  None 

01 =  1 stage (W

1

)

02 =  2 stage (1 compressor 

and 1 auxiliary)

03 =  2 stage (2 compressor and 

no auxiliary)

04 =  3 stage (2 compressor and 

1 auxiliary)

N/A (thermostat 

controlled)

00:  On for cooling (O)

01:  On for heating (B)

02 =  2-pipe FCU

N/A

N/A

N/A

N/A

N/A (thermostat 

controlled)

N/A

00 =  Relay

01 =  0 – 10 V

-

02 =  Floating 

point

00 =  Relay (G1, 

G2, G3)

01 =  0 – 10 V

-

01 =  Heat only

02 =  Cool only

03 =  Changeover

N/A

03 =  4-pipe FCU or 

2-pipe with 

resistive heat

N/A (1 heat stage)

N/A

N/A

N/A (1 cool stage)

N/A (thermostat 

controlled)

N/A

N/A

04 =  Under floor 

hydronic heat

N/A (1 heat stage)

N/A

N/A

N/A

N/A

N/A

00 =  Relay

01 =  0 – 10 V

-

N/A

N/A

01 =  Indoor air only

02 =  Indoor air and floor 

limiting

03 =  Floor temperature only

05 =  Under floor 

electric heat

Bold

 = Factory defaults

Parameter value

Press to go back to 

previous step.

Set

Press to change parameter 

value.

Press to select current 

value and proceed to 

next parameter.

CO =  HVAC controller 

selection mode

Parameter ID

Summary of Contents for HQWT-T-HW

Page 1: ...setpoint 2 After 5 seconds of no activity the setpoint will save and will stop flashing Note Switching between operating modes is not possible while a setpoint is flashing Note By default the setpoints cannot be less than 3 F 2 C apart If a setpoint is adjusted to less than that the other setpoint will automatically change so that there is at least 3 F 2 C difference Heating mode1 2 Auxiliary heat...

Page 2: ...are connected to a 24 36 V power supply E0 shown on the master thermostat The thermostat temperature sensor is not functioning properly Contact Customer Assistance E0 shown on the companion thermostat A companion thermostat will show E0 if the temperature sensor for that zone is missing Check the error code on the master thermostat E1 shown on the master thermostat Wiring issue between the thermos...

Page 3: ...nt CVC avec le SMC55 RESI 3 S allume à la pression de n importe quel bouton S éteint après 10 secondes d inactivité programmable La gestion dynamique du rétro éclairage DBM règle automatiquement l intensité du rétro éclairage selon les conditions de luminosité ambiantes 4 La température ambiante la fonction Arrêt OFF et le mode ventilateur lorsque le ventilateur est en marche sont affichés lorsque...

Page 4: ... est pas alimenté Vérifiez le câblage pour confirmer que le commun noir et V rouge sont raccordés à une alimentation de 24 36 V E0 affiché sur le thermostat principal Le détecteur de température du thermostat ne fonctionne pas correctement Contactez l assistance à la clientèle E0 affiché sur le thermostat auxiliaire Un thermostat auxiliaire affichera E0 si le détecteur de température de cette zone...

Page 5: ...te para la protección del equipo de climatización cuando se utiliza el SMC55 RESI 3 Se enciende cuando se pulsa cualquier botón Se apaga luego de 10 segundos de inactividad programable La gestión de retroiluminación dinámica DBM ajusta automáticamente la intensidad de la luz de fondo basándose en las condiciones de la iluminación ambiental 4 La temperatura ambiente OFF APAGADO y el modo de ventila...

Page 6: ...l termostato maestro se muestra E0 El sensor de temperaturas del termostato no está funcionando correctamente Póngase en contacto con la Asistencia al cliente En el termostato acompañante se muestra E0 Si faltara el sensor de temperatura de esa zona un termostato acompañante mostrará E0 Verifique el código de error en el termostato maestro En el termostato maestro se muestra E1 Problema de conexió...

Page 7: ...otão é premido Desliga se após 10 segundos de inatividade programável A Gestão de Iluminação de Fundo Dinâmica DBM ajusta automaticamente a intensidade da iluminação de fundo baseando se nas condições da iluminação ambiente 4 A temperatura ambiente OFF Desligado e o modo de ventilação quando a ventilação está a funcionar são apresentados quando o sistema está desligado 5 Aux indica que o aquecimen...

Page 8: ...com a assistência técnica E0 é exibido no termostato companion O termostato companion exibirá E0 se não houver sensor de temperatura para aquela zona Verifique o código de erro no termostato principal E1 é exibido no termostato principal Problema de cabeamento entre o termostato e o controlador de HVAC ou o controlador de HVAC está sem energia elétrica Garanta que a linha de comunicação do control...

Page 9: ...tungsmanagement Dynamic Backlighting Management DBM wird die Intensität der Hintergrundbeleuchtung je nach Umgebungslicht automatisch angepasst 4 Zimmertemperatur OFF AUS und Ventilatormodus wenn Ventilator eingeschaltet ist werden angezeigt wenn das System ausgeschaltet ist 5 Aux verweist auf die aktivierte Zusatzheizfunktion in den anderen Heizstufen Only Aux verweist auf die aktivierte Zusatzhe...

Page 10: ... USA Fehlersuche und behebung Problem Mögliche Ursache Lösung Leere Anzeige Das Thermostat hat keinen Strom Verkabelung prüfen um sicherzustellen dass Common schwarz und V rot an eine Stromversorgung mit 24 36 V angeschlossen sind E0 auf der Anzeige des Hauptthermostats Der Thermostatsensor funktioniert nicht richtig Kundendienst benachrichtigen E0 auf der Anzeige des Companion Thermostats Ein Com...

Page 11: ...仍在运行 5 Aux 表示在有其他加热台的情况下辅热正在运行 仅 Aux 表示在无其他加热台 应急加热 的情况下辅热正在运行 6 表示 HVAC 系统时钟事件状态 7 适用模式可通过 HomeWorks QS 软件配置 8 显示屏显示加热或冷却设置点 首次按下升高 降低按钮激活 LCD 背光 再按下升高 降低按钮 调整设置点 9 启用 禁用 HVAC 系统安排 动态背光管理 DBM 传感器位置 恒温器 密封壁箱 和彩色装饰环 将密封壁箱和装饰环用于 所有应用 实心砌体或浇 灌混凝土墙除外 金属壁箱的适配器和螺钉 金属墙盒 EBB 1 SQ 单独出售 的实心砖石或浇筑混 凝土墙中使用金属 墙盒 可拆卸接线端子块 G 4 3 2 1 Auto On G 4 3 2 1 安装 1 关闭QS链路的电源 警告 电击危险 可能会导致严重人身伤害或死亡 在安装或维护本单元之前 请切断所有电源 2 安装墙...

Page 12: ...器没电 检查接线以确认通用线 黑 和 V 红 连接至 24 36 V 电源 主恒温器上出现 E0 恒温器温度传感器未正确运行 联系客户协助 同伴型恒温器上出现 E0 如果该区的温度传感器丢失 则同伴型恒温器将显示 E0 检查主恒温器上的错误代码 主恒温器上显示 E1 恒温器和 HVAC 控制器之间的接线问题或 HVAC 控制器没电 确保 HVAC 控制器通信链路正确连接 并独立于所有其他连接 而且 HVAC 控制 器有电 选择了错误的 HVAC 控制器或通讯协议地址 输入 HVAC 控制器选择模式并选择正确的 HVAC 控制器和通讯协议地址 同伴型恒温器上出现 E1 处理器与 HVAC 控制器之间的接线问题 如果 HVAC 控制器连接至处理器 检查处理器与 HVAC 控制器之间的接线 连接至 HVAC 控制器的 主恒温器从处理器断开连接 确保主恒温器和处理器之间的 QS 链路正确连接 显示...

Reviews: