HSK_operating_manual_English_Ver3.doc
HOMA Pump Technology
-
37
-
Operation temperature range
0 … 50°C
Storage temperature range
-20 … 70°C
Air humidity
0 … 90% RH (non condensing)
Inputs phase loss / phase sequence monitoring
3 x 230/400V +/-10% 50Hz
Switching threshold for phase loss recognition
< 40V at 50Hz
Rechargeable battery
Lead–gel rechargeable battery 12V, 1.2Ah
Charging current of battery
Max: 100 mA
Final charging voltage of accumulator
13.8V
Dimensions of housing (l x b x h)
(without main switch cable glands)
200/300/400 x 200 x 140 mm
Weight
approx. 3 kg
Degree of protection
IP54 (with closed cover)
Cable glands (Maximum amount):
Pump(s)
Mains
Float switch, alarm
Level sensor, alarm, analogue output
equipotential compensation cable
2 x M25 (10…18mm)
1 x M25 (8…14mm)
5 (6) x M16 (4…8mm)
1 x M12 (3…6mm)
Pressure connection
tube
∅
8mm(outer)
∅
6mm(inner)
12.3 Wiring and connecting diagrams
Wiring and connecting diagrams depend on the existing features of the control and are not a part of
this manual. They are enclosed separately. The layout of the wiring terminals X2 of the control board
shows the following picture (HSK25 above; HSK15 below). On the HSK25, terminals 4-20mA+/+ DI1,
DI2 are available only as an option. F1 = fuse (protection) of the control.
F1
SW
HW
SW
1
SW
2
NVS
-
12V
-
4-20
mA-
F1
F1
N
N
P1
TL
P2
TL
P2
TM
P2
TM
P1
TH
P2
TH
P1
Aux1
P1
Aux2
P2
Aux1
P2
Aux2
12
14
11
21
31
34
22
24
32
NVS
+
SW
HW
SW
1
SW
2
12V
+
4-20
mA+ DI1
DI2
X2
F1
SW
HW
SW
1
NVS
-
12V
-
F1
F1
N
N
P1
TL
NC
NC
P2
TM
P1
TH
NC
P1
Aux1
P1
Aux2
NC
NC
12
14
11
21
22
24
NVS
+
SW
HW
SW
1
12V
+
X2
NC
NC
Remarks: Please observe the different terminal connections for the level sensor inputs