
HSK_operating_manual_English_Ver3.doc
HOMA Pump Technology
-
21
-
19 P1aux2
5
0100
(reserved)
-
external resetting of faults (only HSK25)
20 external
5
1000
Input SCHW2 has switched
x
Fault pump 2 (only HSK25)
21 P2T1
6
0001
Thermo contact 1 has tripped
x
22 P2nxT1
6
0010
Thermo contact 1 has tripped several times
n
23 P2T2
6
0100
Thermo contact 2 has tripped
n
24 P2MS
6
1000
Motor starter has tripped
x
25 P2FI
7
0001
RCD (ELCB) has tripped
x
26 P2DI
7
0010
Leakage fault
x
27 P2tmax
7
0100
Pump run time has been exceeded
x
28 P2Imin
7
1000
Pump current too low
x
29 P2Imax
8
0001
Pump current too high
x
30 P2aux1
8
0010
(reserved)
-
31 P2aux2
8
0100
(reserved)
-
32 ---
8
1000
(not
used)
x
Table Fault bits of the HSK
BIN HEX
BIN HEX
0000 1 1000 8
0001 1 1001 9
0010 2 1010 A
0011 3 1011 B
0100 4 1100 C
0101 5 1101 D
0110 6 1110 E
0111 7 1111 F
Conversion of group bits into a hexadecimal digit
6.4.1 Alarm Auto Reset
In this menu, the behaviour of the CPSm in case of faults can be adjusted. Here, two settings for each
fault case are possible. AUTOMATIC reset (mask bit = 0) or MANUAL reset (mask bit = 1).
In the AUTOMATIC position, the fault indication is reset and the control continues to operate, when
the fault is not present any longer.
In the MAN position, indication of all faults is maintained (with the exception of short-term high water).
In order for the controller to continue to operate, all faults must be reset on the controller.
Decide for each fault whether or not an automatic reset should be effected and determine the
corresponding mask word as described above.
A recommendation for adjusting is given in the above table in the column "auto" ( x = automatic reset;
n = no automatic reset; - no recommendation, depending on application).
Security Note: The T2-alarm (thermo contact with higher
tripping temperature) of controllers used in Ex-endangered
areas should not be set to "Auto reset" .