42 Modbus Communications
HP-328
HIT-4G
Register
(Decimal)
Description
Data
Type
Access
Notes
7014
Request Previous
Day Run Time
Seconds
FP32
RO
0 – 86400
7015
Request Previous
Hour Total
FP64
RO
0 – 99999999
7016
Request Previous
Hour Run Time
Seconds
FP32
RO
0 - 3600
7018
Request Hourly
Download
Pointer
FP32
RO
-1 (cleared logs) - 767
7019
Request Daily
Download
Pointer
FP32
RO
-1 (cleared logs) - 383
7020
Request Event
Log Download
Pointer
FP32
R/W -1 (cleared logs) – 344
(To increment by one,
use function code 5)
7022
Fault History
U32
RO
Fault has occurred since
last power on. Each bit
represents a specific
fault defined below.
7023
Active Faults
U32
RO
Fault is currently active.
Each bit represents a
specific fault defined
below.
7050-7051
Request Rate
FP32
RO
Rate stored in two 16-
bit registers
7052-7055 Request Current
Total
FP64
RO
Current Total stored in
four 16-bit registers
Total is reset by sending
a read request to register
9.
7056-7059 Request Grand
Total
FP64
RO
Grand Total stored in
four 16-bit registers
7060-7061
*
Request Current
Total
FP32
RO
Current Total stored in
two 16-bit registers
Total is reset by sending
a read request to register
9.
Summary of Contents for HIT-4G
Page 2: ......
Page 30: ...24 Installation HP 328 HIT 4G This page intentionally left blank...
Page 42: ...Operation 36 HP 328 HIT 4G This page intentionally left blank...
Page 52: ...46 Modbus Communications HP 328 HIT 4G This page intentionally left blank...
Page 68: ...62 HIT 4 Communication Program HP 328 HIT 4G This page intentionally left blank...
Page 71: ...Appendix A Declaration of Conformity 65 HIT 4G HP 328 APPENDIX A DECLARATION OF CONFORMITY...
Page 72: ...66 Appendix A Declaration of Conformity HP 328 HIT 4G...