background image

Hochiki Europe (UK) Ltd – HE-PSU(4.0) Installation Manual 

Page 10 of 10 

2-3-0-997/ISS1/OCT07 

 

 

9. OPERATING INSTRUCTIONS 

The HE-PSU(4.0) is intended for use only as Power Supply Equipment for 24V DC fire detection and alarm 
systems conforming to EN54-2 and EN54-4. 
 
All mounting, installation, commissioning and maintenance should be carried out strictly in accordance with 
the instructions contained in the manual. 
 
Under normal operating conditions, none of the LED indicators should be lit and there should be no output 
on any of the fault output terminals. 
 
Fault conditions are identified by the printed legends on the black ventilated cover of the PSU within the 
enclosure and relate to the on-board LED indicators. 
 
The switched negative fault outputs may be used to operate 24VDC rated relays or indicators up to the 
current limit of 100 milliamps per output.  The reference voltage for the switched negative outputs is the load 
positive. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Hochiki Europe (UK) Ltd 

Grosvenor Road, Gillingham Business Park, 

Gillingham, Kent, ME8 0SA, England 

Telephone: +44(0)1634 260133     Facsimile: +44(0)1634 260132 

Email: [email protected] 

Web: www.hochikieurope.com

 

 

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every 
effort has been made to ensure the accuracy of the information contained within this document it is not warranted or represented by 
Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.  Please check our web site for the latest version of this 
document. 

 

Summary of Contents for HE-PSU(4.0)

Page 1: ...Hochiki Europe UK Ltd HE PSU 4 0 Installation Manual Page 1 of 10 2 3 0 997 ISS1 OCT07 HE PSU 4 0 Power Supply Battery Charger Installation Commissioning Operating Manual...

Page 2: ...sed for fire alarm control and indicating equipment complying with EN54 2 and EN54 4 2 POWER REQUIREMENTS The HE PSU 4 0 requires a mains power supply of 230V AC The maximum input current is 2 Amps Ma...

Page 3: ...rations The operating temperature range should not exceed 5 C to 40 C 2 Humidity levels should not exceed 96 non condensing 3 2 Mounting The HE PSU 4 0 is supplied as an enclosure in portrait orientat...

Page 4: ...readily accessible double pole disconnect device meeting the requirements of EN60950 IEC950 which disconnects live and neutral simultaneously shall be incorporated in the fixed wiring as close to the...

Page 5: ...of even very small capacity are capable of delivering very high currents which can cause fire or injury Battery connections must therefore be done using extreme caution As supplied the HE PSU 4 0 has...

Page 6: ...MF Switch the mains back on and disconnect the battery The load should continue to operate and a negative signal should appear at the terminal BD battery disconnected and the BD LED should light after...

Page 7: ...Page 7 of 10 2 3 0 997 ISS1 OCT07 To do this the batteries should be disconnected and the output voltage measured with a calibrated digital voltmeter The voltage should be within 0 2 volts of the indi...

Page 8: ...upply to the control panel in order that a short circuit in one transmission path will enable the control panel to be supplied with power from the other This is facilitated by the RPSM 1 PCB which is...

Page 9: ...hiki Europe UK Ltd HE PSU 4 0 Installation Manual Page 9 of 10 2 3 0 997 ISS1 OCT07 8 CABLE TERMINATION All cable entries to the enclosure must be via Pirelli AXT20SK Cable terminating kits or equival...

Page 10: ...nd relate to the on board LED indicators The switched negative fault outputs may be used to operate 24VDC rated relays or indicators up to the current limit of 100 milliamps per output The reference v...

Reviews: