Hochiki Europe (UK) Ltd – HE-PSU(4.0) Installation Manual 

Page 2 of 10 

2-3-0-997/ISS1/OCT07 

 

CONTENTS 

1. GENERAL........................................................................................................................2

 

2. POWER REQUIREMENTS .............................................................................................2

 

2.1 HE-PSU(4.0) Input/Output Electrical Ratings .............................................................2

 

2.2 Fuse Ratings ..............................................................................................................3

 

2.3 Batteries .....................................................................................................................3

 

3. INSTALLATION ...............................................................................................................3

 

3.1 Environmental Considerations....................................................................................3

 

3.2 Mounting ....................................................................................................................3

 

3.3 Connecting to the Input ..............................................................................................4

 

3.4 Connecting to the Outputs..........................................................................................4

 

3.4.1 Load Connections (Terminal Block).....................................................................4

 

3.4.2 Load Connections (Ribbon Cable).......................................................................4

 

3.4.3 Battery Connections ............................................................................................5

 

4. COMMISSIONING ...........................................................................................................6

 

5. MAINTENANCE...............................................................................................................6

 

6. MOUNTING .....................................................................................................................8

 

7. WIRING ...........................................................................................................................8

 

8. CABLE TERMINATION ...................................................................................................9

 

9. OPERATING INSTRUCTIONS ......................................................................................10

 

 

1. GENERAL 

The HE-PSU(4.0) is a combined power supply and battery charger designed to be used for fire alarm control 
and indicating equipment complying with EN54-2 and EN54-4. 
 

2. POWER REQUIREMENTS 

The HE-PSU(4.0) requires a mains power supply of 230V AC.  The maximum input current is 2 Amps.  
Mains frequency 50Hz. 
 

2.1 HE-PSU(4.0) Input/Output Electrical Ratings 

Input – 230V AC  
 
Load output - 

19V DC min (battery at minimum), 30 V DC max (mains on) max current 2.5 Amps + 1.5A 

for battery charging. 
 
Maximum ripple 800 millivolts 

 

Battery charging output - 26.4 VDC (at 40°C) 28.9 V DC (at -5°C) 1.5 Amps.  
 
Fault signals -  switched negative open collector (with respect to load positive) current limited 100mA max. 
 

 

Mains fail 

 

 

Battery disconnected (Low battery shut off voltage - 19 V (+/- 1 volt)) 

 

 

Battery low (Low battery warning voltage - 21 V (+/- 1 volt)) 

 

 

Earth fault 

 

 

Charger fault (high output to battery) 

 

 

Fail safe (any one of the above) 

 
These outputs are protected against short circuits. 

Summary of Contents for HE-PSU(4.0)

Page 1: ...Hochiki Europe UK Ltd HE PSU 4 0 Installation Manual Page 1 of 10 2 3 0 997 ISS1 OCT07 HE PSU 4 0 Power Supply Battery Charger Installation Commissioning Operating Manual...

Page 2: ...sed for fire alarm control and indicating equipment complying with EN54 2 and EN54 4 2 POWER REQUIREMENTS The HE PSU 4 0 requires a mains power supply of 230V AC The maximum input current is 2 Amps Ma...

Page 3: ...rations The operating temperature range should not exceed 5 C to 40 C 2 Humidity levels should not exceed 96 non condensing 3 2 Mounting The HE PSU 4 0 is supplied as an enclosure in portrait orientat...

Page 4: ...readily accessible double pole disconnect device meeting the requirements of EN60950 IEC950 which disconnects live and neutral simultaneously shall be incorporated in the fixed wiring as close to the...

Page 5: ...of even very small capacity are capable of delivering very high currents which can cause fire or injury Battery connections must therefore be done using extreme caution As supplied the HE PSU 4 0 has...

Page 6: ...MF Switch the mains back on and disconnect the battery The load should continue to operate and a negative signal should appear at the terminal BD battery disconnected and the BD LED should light after...

Page 7: ...Page 7 of 10 2 3 0 997 ISS1 OCT07 To do this the batteries should be disconnected and the output voltage measured with a calibrated digital voltmeter The voltage should be within 0 2 volts of the indi...

Page 8: ...upply to the control panel in order that a short circuit in one transmission path will enable the control panel to be supplied with power from the other This is facilitated by the RPSM 1 PCB which is...

Page 9: ...hiki Europe UK Ltd HE PSU 4 0 Installation Manual Page 9 of 10 2 3 0 997 ISS1 OCT07 8 CABLE TERMINATION All cable entries to the enclosure must be via Pirelli AXT20SK Cable terminating kits or equival...

Page 10: ...nd relate to the on board LED indicators The switched negative fault outputs may be used to operate 24VDC rated relays or indicators up to the current limit of 100 milliamps per output The reference v...