HCA Series Installation Manual
Page 26 of 58
V2.15
4.1.2 System Normal Status Screen
When the control panel condition is normal standby (no active alarms, troubles, etc.), it displays one of
two system normal screens:
16/03 13:17:03
SYSTEM NORMAL
European time and date format
03/16 01:17:03pm
SYSTEM NORMAL
American time and date format
4.1.3 Off Normal System Status Screens and Sounds
During off normal alarm, trouble, or supervisory conditions, the piezoelectric sounder provides separate
and distinct sounds as follows:
Alarm
– On for 1.25 seconds, Off for 0.25 seconds, repeat.
Supervisory
– On for 0.75 seconds, Off for 0.75 seconds, repeat.
Trouble
– On for 0.4 seconds, Off for 0.4 seconds, repeat.
When alarms, supervisories and troubles are active at the same time, the alarm pattern is the highest
priority, followed by supervisory and then trouble.
4.1.4 Zone Alarm and/or Trouble Screens
The screen below is displayed when at least one zone is in trouble or alarm.
Z1 2 3 4 5 6 7 8
N A T N S D N A
This screen is activated whenever an off normal condition exists for one or
more zones. For any zone in alarm, the zone status letter will blink on and
off.
The possible symbols appearing on the bottom line are:
N
zone enabled and operating correctly (normal standby)
D
zone disabled
T
zone enabled and in trouble condition
S
zone in supervisory condition
A
zone in non-release alarm condition
P
zone in pre-release alarm condition
R
zone in release alarm condition
B
indicates an Abort (Bypass) condition during an active release sequence countdown
4.1.5 System TROUBLE Screens
The screens below are displayed during the following system trouble conditions:
NO BATTERY
This screen is displayed when there is no battery connected.
LOW BATTERY
This screen is displayed when the battery is not fully charged.