b) Verify the Input Voltage Configuration
The GPU may be configured for various input voltages, depending on the specific model
(specification number). The factory pre-configures each unit before shipment according to the
customer specifications for the input voltage. While the GPU is open for connecting cables, verify the
voltage configuration. Figure 2 shows the interior panel as viewed from the right side of the GPU.
Figure 2 Input Voltage Configuration Locations
On the left is Voltage Changeover Panel, which sets the input voltage for the main transformer. On
the right is the control transformer, which has different taps for the various input voltages.
(1) Make sure the GPU is not connected to the electrical service.
(2) Remove the top cover.
(3) Locate the items pictures in Figure 2.
(4) Refer to Sheet 6 of the schematic diagram, which is located in Chapter 5 of this manual.
(5) Verify that the configuration matches the appropriate diagram on the schematic.
CAUTION
Reconnection of control transformer as well as main input connection panel must be
made when changing rated input voltage. See changeover diagram.
Changing the voltage configuration requires changes to main transformer T1 configuration on the
Changeover Board and changes to control transformer T2 by moving a yellow wire to a different tap
on the right side of the transformer. (See Figure 2)
Input Power Contactor
Control Transformer TR
Voltage Changeover
Board
Summary of Contents for GPU-600 Series
Page 2: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......