OM-2244 / Operation and Maintenance Manual
DCS-600/ Series 500082 / Solid State Transformer-Rectifiers
December 15, 2014
Chapter 2-2
Page 4
Test Point
Function
Signal Controlled by:
TP1
SCR Gate Pulse Phase 3
R10
TP2
SCR Gate Pulse Phase 2
R9
TP3
PC Board Common
TP4
+10.0 VDC Timer Voltage
TP5
+15 V Regulated Voltage
TP6
–15 V Regulated Voltage
TP7
+24 V Unregulated Voltage
TP8
SCR Gate Pulse Phase 1
TP13
Actual Output Voltage (28.5 or 14.25)
R109 (-28.5 V) or
R110 (-14 V)
TP14
Null at zero output current: provides amplified
load amp reading for comparison with
overload limit (TP20) and starting amperage
limit (TP21) set by R13 control on front panel.
R38
TP15
PC Board Common
TP17
Voltage Slope Test Point
R102
TP19
Reference Volt Test Point
R101
TP20
Overload Limit
R60
TP21
Starting Current
R13 (front panel)
TPD
SCR Gate Timer Output Phase 3
TPE
SCR Gate Timer Output Phase 2
TPF
SCR Gate Timer Output Phase 1
TPL
Overload Trip Summing Point
Table 1
GPU Circuit Board Test Points and Controls
Summary of Contents for GPU-600 Series
Page 2: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......