NOTE: The 4 to 12 second time delay is generally set at 5 seconds.
(d) If the undervoltage circuit performs satisfactorily, return the unit to normal operation by adjust-
ing the voltage to 115 V, pressing the reset switch, and closing the load contactor.
(39) Check underfrequency sensing relay, protective monitor, and indicating light. At some frequency
value
(Hz, cycles-per-second)
from 385 Hz down to 375 Hz, the underfrequency sensing relay should
function to signal the underfrequency circuit in the protective monitor module to OPEN the load con-
tactor holding circuit, thus OPENING the load contactor. To check the underfrequency protective com-
ponents, proceed as follows:
(a) While the unit is operating normally under load, reduce generator output frequency by reduc-
ing engine speed. Use the governed speed setting potentiomete. Turn adjusting screw COUN-
TERCLOCKWISE gradually to reduce engine speed until frequency meter indicates 386 Hz.
Underfrequency protective relay should not function to open the load contactor at this frequency.
Reduce frequency in steps of 1 Hz.
(b) If the protective system functions to open the load contactor and turn on the underfrequency
light
(13)
after some frequency between 385 Hz and 375 Hz is reached, all components of the
system are functioning properly. If the load contactor is not opened within the above frequency
range, refer to Trouble Shooting Chart to determine which component is defective.
(c) Return unit to normal operating condition.
(40) Check overfrequency sensing relay, protective monitor, and indicating light. This protective circuit
operates in exactly the same manner as the underfrequency circuit except its operating range is from
415 Hz to 425 Hz. Its purpose also is to open the load contactor and turn on an indicating light.
(a) Check procedures are the same for overfrequency as for underfrequency
(above)
except that
engine speed is INCREASED to create a condition of overfrequency.
(b) If the overfrequency system functions to open the load contactor and turn on the overfre-
quency light (
14)
after some frequency between 415 Hz and 425 Hz is reached, all components
of the system are functioning properly. If the load contactor is not opened within the above fre-
quency range, refer to Trouble Shooting Chart to determine which component is defective.
(41) If the generator is operating under load at this point, place the contactor control switch
(18, Fig.
1)
in OFF position to open load contactor and disconnect load. There will be no further need for the
load bank in the following checks.
(42) With the engine running at normal governed speed, check the entire unit for vibration and for any
parts which may have become loosened during the above checks. Tighten any loose attaching hard-
ware as required.
(43) Check 400-Hz generator bearings. Use a stethoscope or metal sounding rod to listen for unusual
noises. If using a metal rod, place one end on the generator housing and hold the other end near the
ear. Hold the rod with three fingers and use the index finger and thumb to form a “sounding chamber”
between the rod and the ear. Do NOT allow the rod to touch the ear. Listen for “grinding” or pounding
sounds which would indicate a defective bearing. An engine noise may be “telegraphed” to the gener-
ator and misinterpreted as a generator noise. Send the unit to overhaul if in doubt of bearing service-
ability.
WARNING: ELECTRIC SHOCK, MOVING PARTS, AND NOISE CAN KILL OR
INJURE! IF A METAL SOUNDING ROD IS USED TO DETECT BEARING
NOISES, EXERCISE EXTREME CARE TO AVOID INJURY.
OM-2029
September 30/89 Revised
2-3
Page 7
Summary of Contents for 140GT17K
Page 2: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank OM 2029 Addendum June 6 90 Page 4 ...
Page 17: ......
Page 18: ......
Page 42: ...Output Terminal Panel Figure 11 OM 2029 1 1 September 30 89 Revised Page 24 ...
Page 46: ...This page intentionally left blank OM 2029 1 2 September 30 89 Revised Page 4 ...
Page 74: ...This page intentionally left blank OM 2029 2 2 September 30 89 Revised Page 6 ...
Page 122: ...Generator Set Figure 1 OM 2029 4 3 September 30 89 Revised Page 2 ...
Page 126: ...This page intentionally left blank 4 3 July 27 90 Page 3C OM 2029 ...
Page 128: ...Canopy Assembly Figure 2 OM 2029 4 3 September 30 89 Revised Page 4 ...
Page 130: ...Generator Set Without Canopy Figure 3 OM 2029 4 3 September 30 89 Revised Page 6 ...
Page 132: ...This page intentionally left blank OM 2029 4 3 September 30 89 Revised Page 8 ...
Page 134: ...Radiator and Cooling System Group Figure 4 OM 2029 4 3 September 30 89 Revised Page 10 ...
Page 136: ...Air Cleaner Assembly Figure 5 OM 2029 4 3 September 30 89 Revised Page 12 ...
Page 138: ...Electric Governor Kit Figure 6 OM 2029 4 3 September 30 89 Revised Page 14 ...
Page 140: ...Panel Engine Control Assembly Figure 7 OM 2029 4 3 September 30 89 Revised Page 16 ...
Page 142: ...Generator Control Box Assembly Figure 8 4 3 July 27 90 Page 18 OM 2029 ...
Page 144: ...This page intentionally left blank OM 2029 4 3 September 30 89 Revised Page 20 ...
Page 146: ...Stator Terminal Panel Assembly Figure 9 OM 2029 4 3 September 30 89 Revised Page 22 ...
Page 148: ...Power Module Panel Assembly Figure 10 OM 2029 4 3 September 30 89 Revised Page 24 ...
Page 150: ...Generator Group Figure 11 OM 2029 4 3 September 30 89 Revised Page 26 ...
Page 152: ...Fuel Line Assembly Figure 12 OM 2029 4 3 September 30 89 Revised Page 28 ...
Page 156: ...This page intentionally left blank 4 3 March 16 90 Page 32 OM 2029 ...
Page 158: ...This page intentionally left blank 4 3 March 16 90 Page 34 OM 2029 ...
Page 160: ...Brake Kit Assembly Figure 14 4 3 March 16 90 Page OM 2029 ...
Page 162: ...This page intentionally left blank 4 3 March 16 90 Page 38 OM 2029 ...
Page 168: ...This page intentionally left blank 4 3 July 27 90 Page 44 OM 2029 ...
Page 178: ...This page intentionally left blank OM 2029 4 4 September 30 89 Revised Page 10 ...
Page 180: ...This page intentionally left blank OM 2029 5 0 September 30 89 Revised Page 2 ...
Page 182: ...This page intentionally left blank OM 2029 6 0 September 30 89 Revised Page 2 ...
Page 184: ...This page intentionally left blank OM 2029 Unusual Service Conditions September 30 89 Page 2 ...
Page 185: ......
Page 186: ......