OM-2228 / Operation and Maintenance Manual
120CU20 / Series 500120 / 400 Hz. Generator Set
October 15, 2013
Chapter 2-3
Page 11
Figure 6: Engine Interface PC Board.
(4) The fault code will flash in the following sequence:
First, a “Check Engine” (yellow) lamp will flash. There will be a short 1- or 2-second pause after
which the number of the recorded fault code will flash in the “Engine Stop” (red) lamp. There will
be a 1- or 2-second pause between each number. When the number has finished flashing in the
red lamp, the yellow lamp will appear again. The fault code will repeat in the same sequence.
The lamps flash each fault code 3 times before advancing to the next code. To skip to the next
fault code, move the Engine Codes Switch momentarily to the UP position. You can go back to
the previous fault code by momentarily moving the Engine Codes Switch to the DOWN position.
If only one fault is recorded, the QSB control system will continuously display the same fault code
when the Engine Codes Switch is moved to either the UP or DOWN position.
(5) See engine manufacture’s manual for code meanings.
Summary of Contents for 120CU20
Page 2: ... ...
Page 4: ... ...
Page 205: ......
Page 206: ......
Page 207: ......
Page 208: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......